Connecting accessories
Ripple-control receiver (Solar-Log1000 PM+)
Solar-Log
1000/500/200
Installation 135 of 268
5.5 Ripple-control receiver (Solar-Log
1000
PM+)
The Solar-Log
1000
PM+ has an additional interface for connecting up to two
ripple-control receivers. Ripple-control receivers can send the signals for 4-
step effective power reduction.
For power reduction and reactive power control, an additional contact can be
used to distinguish between the signals from two different ripple-control receivers.
Wiring
The outputs of the ripple-control receiver can be connected through 4 poten-
tial-free contacts.
Terminal block connector Solar-Log
1000
PM+
Ripple-control receiver step
Terminal
Terminal
+5 V
2 (+12 V)
Level 1 (100%)
3 (GND)
Level 2 (60%)
4 (Data)
Level 3 (30%)
5
Level 4 (0%)
+5 V

Note
You can find examples of the cabling for ripple-control receivers on our website:
www.solar-log.com
The rest of the configuration of the power management is carried out on the
web-interface of the Solar-Log
1000
PM+, in the
Configuration/Extended/Power management dialogue box ( Page 182).
Zobrazit stránku 134
1 2 ... 130 131 132 133 134 135 136 137 138 139 140 ... 267 268

Komentáře k této Příručce

Žádné komentáře

ReliOn RCM-832N manuals

Owner’s manuals and user’s guides for Humidifiers ReliOn RCM-832N.
We providing 1 pdf manuals ReliOn RCM-832N for download free by document types: User Manual






More products and manuals for Humidifiers ReliOn

Models Document Type
None