VLT® 6000 HVAC1MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACContents ProgrammingAll aboutVLT 6000 HVACInstallationIntrIn
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark10 Better regulationIf a frequency converter is used for regulating the flowor p
VLT® 6000 HVAC100★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC101MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC102★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC103MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC104★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC105MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC106★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC107MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC108★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC109MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC11MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACWWWWWithout a frithout a frithout a frithout a frithout a frequ
VLT® 6000 HVAC110★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC111MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC112★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC113MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC114★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC115MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC116★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC117MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC118★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC119MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark121. Mains voltage3 x 200 - 240 V AC, 50 / 60 Hz3 x 380 - 460 V AC, 50 / 60 Hz.2. Rec
VLT® 6000 HVAC120★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC121MG.60.B1.02 - VLT is a registered Danfoss trademarkProgramming Serial communication for FC protocolMasterSlave 31 (126)Slave 2Slave
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark122- - - - - -- - - - - -MastertelegramSlavetelegramPausetimeResponse-timePausetimeEa
VLT® 6000 HVAC123MG.60.B1.02 - VLT is a registered Danfoss trademarkProgramming Data character (byte)The build-up of data blocks depends on the type
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark1241. Parameter bytes1514131211109876543210Parameter commands and replies (AK)Bits no
VLT® 6000 HVAC125MG.60.B1.02 - VLT is a registered Danfoss trademarkProgrammingLowbyteHighbyteExample - Index:The first error code (index [1]) in para
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark126PKEINDPWEHIGHPWELOWPKEINDPWEHIGHPWELOWPKEINDPWEHIGHPWELOWPKEINDPWEHIGHPWELOWParame
VLT® 6000 HVAC127MG.60.B1.02 - VLT is a registered Danfoss trademarkProgramming PCD1 PCD2Control telegram Control word Reference value(master➝slave)Re
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark128Bit 03, Coasting stop:Bit 03 = "0" means that the VLT frequency converte
VLT® 6000 HVAC129MG.60.B1.02 - VLT is a registered Danfoss trademarkProgramming Status word as per FC protocolThe status word is used to inform t
VLT® 6000 HVAC13MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACGood torque control properties, smooth transition tocurrent lim
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark130Example - control word andserial communication ref.:The VLT frequency converter mu
VLT® 6000 HVAC131MG.60.B1.02 - VLT is a registered Danfoss trademarkProgramming Present output frequencySlave➝Master1514131211109876543210Bit no.
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark132✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVAC133MG.60.B1.02 - VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark134✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVAC135MG.60.B1.02 - VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark136✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVAC137MG.60.B1.02 - VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark138✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVAC139MG.60.B1.02 - VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark14Advanced motor protectionVLT 6000 HVAC features integrated electronic,thermal motor
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark140✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVAC141MG.60.B1.02 - VLT is a registered Danfoss trademark✭ = factory setting. ( ) = parameter window text. [ ] = value for use in communica
VLT® 6000 HVAC142★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC143MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC144★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC145MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC146★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regi
VLT® 6000 HVAC147MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via
VLT® 6000 HVAC148MG.60.B1.02 - VLT is a registered Danfoss trade mark Status messagesStatus messages appear in the 4th line of the display- see e
VLT® 6000 HVAC149MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACStatus messages, cont.Freeze output request (FRZ.REQ.)A sta
VLT® 6000 HVAC15MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACPC software and serial communicationDanfoss offers various opti
VLT® 6000 HVAC150MG.60.B1.02 - VLT is a registered Danfoss trade mark List of warnings and alarmsThe table gives the different warnings and alarm
VLT® 6000 HVAC151MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVAC WarningsA warning will flash in line 2, while an expl
VLT® 6000 HVAC152MG.60.B1.02 - VLT is a registered Danfoss trade markWarnings and alarms, cont.WARNING/ALARM 8Undervoltage (DC LINK UNDERVOLT)If the i
VLT® 6000 HVAC153MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACASYMMETRICAL IMPEDANCE [2]AMA has detected an asymmetrical
VLT® 6000 HVAC154MG.60.B1.02 - VLT is a registered Danfoss trade markALARM: 32Motor phase W missing(MISSING MOT.PHASE U):Motor phase W between VLT fre
VLT® 6000 HVAC155MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACWARNING: 41MOTOR TOO BIG (MOTOR TOO BIG)The motor used is p
VLT® 6000 HVAC156MG.60.B1.02 - VLT is a registered Danfoss trade mark Aggressive environmentsIn common with all electronic equipment, a VLTfreque
VLT® 6000 HVAC157MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACGalvanic isolation Galvanic isolation (PELV)PELV offer
VLT® 6000 HVAC158MG.60.B1.02 - VLT is a registered Danfoss trade mark Extreme running conditionsShort circuitVLT 6000 HVAC is protected against s
VLT® 6000 HVAC159MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACIf very small motors are used without phase coilinsulation,
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark16 CE-labellingWhat is CE-labelling ?What is CE-labelling ?What is CE-labelling
VLT® 6000 HVAC160MG.60.B1.02 - VLT is a registered Danfoss trade mark Derating for ambient temperatureThe ambient temperature (TAMB,MAX) is the m
VLT® 6000 HVAC161MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVAC Derating for running at low speedWhen a centrifugal p
VLT® 6000 HVAC162MG.60.B1.02 - VLT is a registered Danfoss trade mark EfficiencyTo reduce energy consumption it is very important tooptimize the
VLT® 6000 HVAC163MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACThe voltage distortion on the mains supply dependson the si
VLT® 6000 HVAC164MG.60.B1.02 - VLT is a registered Danfoss trade mark EMC test results (Emission, Immunity)The following test results have been o
VLT® 6000 HVAC165MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACClass A-1:Equipment used in a manufacturing environment.Cla
VLT® 6000 HVAC166MG.60.B1.02 - VLT is a registered Danfoss trade markDM: Differential modeCM: Common modeCCC: Capacitive clamp couplingDCN: Direct cou
VLT® 6000 HVAC167MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACDigital inputs:The digital inputs can be used for controlli
VLT® 6000 HVAC168MG.60.B1.02 - VLT is a registered Danfoss trade markLSB:Least significant bit.Used in serial communication.MCM:Stands for Mille Circu
VLT® 6000 HVAC169MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACDatatype Factory settingsConversionindexPNU Parameter
VLT® 6000 HVAC17MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC Application examplesThe next few pages give typical examp
VLT® 6000 HVAC170MG.60.B1.02 - VLT is a registered Danfoss trade markPNU Parameter Factory setting Range Changes 4-Setup# description during operation
VLT® 6000 HVAC171MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACPNU Parameter Factory setting Range Changes 4-Setup# descri
VLT® 6000 HVAC172MG.60.B1.02 - VLT is a registered Danfoss trade mark Factory settingsDatatype56566665555445554455667666Conversionindex00-10-1-10
VLT® 6000 HVAC173MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACPNU Parameter Factory setting Range Changes 4-Setup# descri
VLT® 6000 HVAC174MG.60.B1.02 - VLT is a registered Danfoss trade markPNU Parameter Factory setting Range Changes 4-Setup# description during operation
VLT® 6000 HVAC175MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACAAcoustic noise ...
VLT® 6000 HVAC176MG.60.B1.02 - VLT is a registered Danfoss trade markHHand start...
VLT® 6000 HVAC177MG.60.B1.02 - VLT is a registered Danfoss trade markAll aboutVLT 6000 HVACTTechnical dataGeneral technical data ...
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark18 Variable Air VolumeVAV or Variable Air Volume systems, are used tocontrol bot
VLT® 6000 HVAC19MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC Constant Air VolumeCAV, or Constant Air Volume systems ar
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark2ProgrammingProgrammingProgrammingProgrammingProgrammingControl unit LCP...
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark20Water InletWater OutletCHILLERTemperatureSensorBASINConderserWater pumpSupply
VLT® 6000 HVAC21MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACWater InletWater OutletCHILLERBASINConderserWater pumpSupplyTem
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark22 Primary pumpsPrimary pumps in a primary/secondary pumpingsystem can be used t
VLT® 6000 HVAC23MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC Secondary pumpsSecondary pumps in a primary/secondary chi
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark24 Specification textThe following is a proposal for a HVAC frequencyconverter s
VLT® 6000 HVAC25MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC1.06 Quality AssuranceA. The frequency converters shall be manu
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark262.05 Protective FeaturesA. Class 20 I2t electronic motor overload protectionfor sin
VLT® 6000 HVAC27MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC2.06 ControlA. Hand/Off/Auto selector switches shall be provide
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark28V. The frequency converter will sense the loss of loadand signal a no load/broken
VLT® 6000 HVAC29MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC3.03 ExaminationA. Contractor to verify that job site condition
VLT® 6000 HVAC3MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACThis Design Guide can be used with all VLT 6000 HVAC fre-quency
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark30 Ordering guideThis section makes it easier for you to specify andorder a VLT
VLT® 6000 HVAC31MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACMains voltage 380 - 415 VTypical shaft outputMax continuous out
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark32 EnclosureVLT 6000 HVAC is available with the followingenclosures:- IP 00: 30
VLT® 6000 HVAC33MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC Fieldbus protocolsDanfoss VLT frequency converters are ab
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark34 Unpacking and ordering a VLT frequencyconverterAre you are in doubt as to whi
VLT® 6000 HVAC35MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC▲▲▲▲▲ Ordering form VLT 6000 HVACPower sizese.g. 6008Appli
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark36Control unitLCPOPTIONS1) IP 4x/NEMA 1 top cover is for IP 20 units only and onlyhor
VLT® 6000 HVAC37MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC LC filters for VLT 6000 HVACWhen a motor is controlled by
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark38 Ordering numbers, LC filter modulesMains supply 3 x 200 - 240 VMains supply 3
VLT® 6000 HVAC39MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC LC filters 6002-6006, 200 - 240 V / 6002-6011 380 - 460 V
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark4Warning:Touching the electrical parts may be fatal - even after theequipment has bee
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark40The table and the drawing give the measurements ofIP 00 LC filters for Compact unit
VLT® 6000 HVAC41MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACLC-filter IP 20LC type A [mm] B [mm] C [mm] D [mm] E [mm] F [mm
VLT® 6000 HVAC42MG.60.B1.02 - VLT is a registered Danfoss trade mark General technical dataMains supply (L1, L2, L3):Supply voltage 200-240 V uni
VLT® 6000 HVAC43MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation General technical dataControl card, pulse input:No. of programma
VLT® 6000 HVAC44MG.60.B1.02 - VLT is a registered Danfoss trade mark General technical dataCable lengths and cross-sections:Max. motor cable leng
VLT® 6000 HVAC45MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation Mains supply 3 x 200 - 240 VAccording to international requirem
VLT® 6000 HVAC46MG.60.B1.02 - VLT is a registered Danfoss trade markVLVLVLVLVLT typeT typeT typeT typeT type600260026002600260026003600360036003600360
VLT® 6000 HVAC47MG.60.B1.02 - VLT is a registered Danfoss trade markInstallationVLVLVLVLVLT typeT typeT typeT typeT type607560756075607560756100610061
VLT® 6000 HVAC48MG.60.B1.02 - VLT is a registered Danfoss trade mark Mechanical dimensionsAll measurements in mm.VLT type A B C a b a/b TypeBooks
VLT® 6000 HVAC49MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation Mechanical dimensions
VLT® 6000 HVAC5MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC Introduction to the Design GuideThis Design Guide is a too
VLT® 6000 HVAC50MG.60.B1.02 - VLT is a registered Danfoss trade mark Mechanical installationPlease pay attention to the requirementsthat apply to
VLT® 6000 HVAC51MG.60.B1.02 - VLT is a registered Danfoss trade markInstallationSide-by-sideVLT 6075-6275 IP 00 and IP 20All IP 00 and IP 20 units in
VLT® 6000 HVAC52MG.60.B1.02 - VLT is a registered Danfoss trade mark High voltage warningThe voltage of the frequency converter is dangerous when
VLT® 6000 HVAC53MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation RFI switchMains supply isolated from earth:When the VLT frequenc
VLT® 6000 HVAC54MG.60.B1.02 - VLT is a registered Danfoss trade mark EMC-correct electrical installationGeneral points to be observed to ensure E
VLT® 6000 HVAC55MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation Use of EMC-correct cablesScreened/armoured cables are recommende
VLT® 6000 HVAC56MG.60.B1.02 - VLT is a registered Danfoss trade mark Earthing of screened/armoured control cablesGenerally speaking, control cabl
VLT® 6000 HVAC57MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation VLT 6000 HVAC enclosuresBookstyle IP 20VLT 6002-6005, 200-240 VV
VLT® 6000 HVAC58MG.60.B1.02 - VLT is a registered Danfoss trade mark VLT 6000 HVAC enclosuresIP 54VLT 6006-6032, 200-240 VVLT 6016-6062, 380-460
VLT® 6000 HVAC59MG.60.B1.02 - VLT is a registered Danfoss trade markInstallationIP 20VLT 6150-6275, 380-460 VIP 00VLT 6150-6275, 380-460 VIP 54VLT 615
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark6Installation:Installation:Installation:Installation:Installation: This section shows
VLT® 6000 HVAC60MG.60.B1.02 - VLT is a registered Danfoss trade markCompact IP 20/IP 54VLT 6002-6005, 200-240 VVLT 6002-6011, 380-460 VIP 20VLT 6006-6
VLT® 6000 HVAC61MG.60.B1.02 - VLT is a registered Danfoss trade markInstallationIP 54VLT 6150-6275, 380-460 VIP 00/20VLT 6150-6275, 380-460 VIP 00/20V
VLT® 6000 HVAC62MG.60.B1.02 - VLT is a registered Danfoss trade mark Tightening-up torque and screw sizesThe table shows the torque required when
VLT® 6000 HVAC63MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation Motor cablesSee Technical data for correct sizing of motor cable
VLT® 6000 HVAC64MG.60.B1.02 - VLT is a registered Danfoss trade mark DC bus connectionThe DC bus terminal is used for DC back-up, with theinterme
VLT® 6000 HVAC65MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation Electrical installation, control cablesTorque: 0.5 - 0.6 Nm.Scre
VLT® 6000 HVAC66MG.60.B1.02 - VLT is a registered Danfoss trade mark Connection example, VLT 6000 HVACThe diagram below gives an example of a typ
VLT® 6000 HVAC67MG.60.B1.02 - VLT is a registered Danfoss trade markInstallation Switches 1-4The dipswitch is located on the control card.It is u
VLT® 6000 HVAC68MG.60.B1.02 - VLT is a registered Danfoss trade mark Connection examplesSingle-pole start/stop- Start/stop using terminal 18.Para
VLT® 6000 HVAC69MG.60.B1.02 - VLT is a registered Danfoss trade markProgramming Control unit LCPThe front of the VLT frequency converter features
VLT® 6000 HVAC7MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVAC Available literatureThe chart below gives an overview of t
VLT® 6000 HVAC70MG.60.B1.02 - VLT is a registered Danfoss trade mark[+/-] is used for selecting parameters andfor changing a chosen parameter. Theseke
VLT® 6000 HVAC71MG.60.B1.02 - VLT is a registered Danfoss trade markProgramming Display mode, cont.The table below gives the operating data optio
VLT® 6000 HVAC72MG.60.B1.02 - VLT is a registered Danfoss trade markDisplay mode II Display mode III:This display mode can be generated as long a
VLT® 6000 HVAC73MG.60.B1.02 - VLT is a registered Danfoss trade markProgramming Changing dataRegardless of whether a parameter has been selectedu
VLT® 6000 HVAC74MG.60.B1.02 - VLT is a registered Danfoss trade markQuick menu: Parameter 1 of 12Used to select the language for the display.Quick men
VLT® 6000 HVAC75MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC76★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC77MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC78★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC79MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVACMG.60.B1.02 - VLT is a registered Danfoss trademark8Why use a frequency converter for controllingfans and pumps?A frequency converter ta
VLT® 6000 HVAC80★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC81MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC82★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC83MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC84★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC85MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC86★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC87MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC88★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC89MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC9MG.60.B1.02 - VLT is a registered Danfoss trademarkIntroduction to HVACExample with varying flow over 1 yearThe example below is calcul
VLT® 6000 HVAC90★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC91MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC92★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC93MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC94★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC95MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC96★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC97MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s
VLT® 6000 HVAC98★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication portMG.60.B1.02 - VLT is a regis
VLT® 6000 HVAC99MG.60.B1.02 - VLT is a registered Danfoss trade mark★ = factory setting. ( ) = display text [ ] = value for use in communication via s