Danfoss VLT 6000 HVAC Servisní příručka Strana 114

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 177
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 113
VLT
®
6000 HVAC
114
= factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
MG.60.B1.02 - VLT is a registered Danfoss trade mark
PID for process regulation, cont.
Inverse regulation
Normal regulation means that the motor speed
increases when the reference/setpoint is higher than
the feedback signal. If there is a need for inverse
regulation, in which the speed is reduced when the
feedback signal is lower than the reference/setpoint,
Inverse must be programmed in parameter 420 PID
normal/inverse control.
Anti Windup
The process regulator is factory preset with an active
anti-windup function. This function ensures that
when either a frequency limit, current limit or voltage
limit is reached, the integrator will be initialised for a
frequency that corresponds to the present output
frequency. This avoids integration on a deviation
between the reference/setpoint and the actual state
of the process, the controller of which is not possible
by means of a speed change. This function can be
disabled in parameter 421 PID anti windup.
Start-up conditions
In some applications, optimum setting of the process
regulator will mean that it takes an excessive time for
the required process state to be reached. In such
applications it might be an advantage to fix an output
frequency to which the VLT frequency converter is to
bring the motor before the process regulator is
activated. This is done by programming a PID start-
up frequency in parameter 422.
Differentiator gain limit
If there are very quick variations in a given application
with respect to the reference/setpoint signal or the
feedback signal, the deviation between reference/
setpoint and the actual process state will quickly
change. The differentiator may thus become too
dominant. This is because it reacts to the deviation
between the reference/setpoint and the actual
process state. The quicker the deviation changes, the
stronger the resulting differentiator frequency
contribution. The differentiator frequency contribution
can thus be limited to allow the setting of a
reasonable differentiation time for slow changes and
a suitable frequency contribution for quick changes.
This is done in parameter 426, PID Differentiator gain
limit.
Lowpass filter
If there are ripple currents/voltages on the feedback
signal, these can be dampened by means of a built-in
lowpass filter. Set a suitable lowpass filter time
constant. This time constant represents the limit
frequency of the ripples occurring on the feedback
signal.
If the lowpass filter has been set to 0.1s, the limit
frequency will be 10 RAD/sec., corresponding to (10/
2 x π) = 1.6 Hz. This means that all currents/voltages
that vary by more than 1.6 oscillations per second will
be removed by the filter.
In other words, regulation will only be carried out on a
feedback signal that varies by a frequency of less than
1.6 Hz. Choose a suitable time constant in parameter
427, PID Lowpass filter time.
Optimisation of the process regulator
The basic settings have now been made; all that
remains to be done is to optimise the proportional
gain, the integration time and the differentiation time
(parameters 423, 424 and 425). In most processes,
this can be done by following the guidelines given
below.
1. Start the motor.
2. Set parameter 423 PID proportional gain to 0.3
and increase it until the process shows that the
feedback signal is unstable. Then reduce the value
until the feedback signal has stabilised. Now lower
the proportional gain by 40-60%.
3. Set parameter 424 PID integration time to 20 s
and reduce the value until the process shows that
the feedback signal is unstable. Increase the
integration time until the feedback signal
stabilises, followed by an increase of 15-50%.
4. Parameter 425 PID differentiation time is only used
in very fast-acting systems. The typical value is
four times the value set in parameter 424 PID
Integration time. The differentiator should only be
used when the setting of the proportional gain
and the integration time have been fully optimised.
NB!
If necessary, start/stop can be activated a
number of times in order to provoke an
unstable feedback signal.
Zobrazit stránku 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 176 177

Komentáře k této Příručce

Žádné komentáře