Make sure not to supply too high a braking
current for too long, since otherwise the
motor will be damaged because of
mechanical overload or the heat generated in the
motor.
115 DC braking time
(DC BRAKE TIME)
Value:
0.0 - 60.0 sec. ✭ 10.0 sec.
Function:
This parameter is for setting the DC braking time for
which the DC braking current (parameter 113) is to
be active.
Description of choice:
Set the desired time.
116 DC brake cut-in frequency
(DC BRAKE CUT-IN)
Value:
0.0 (OFF) - par. 202 Output frequency
high limit, f
MAX
✭ OFF
Function:
This parameter is used for setting the DC brake cut-in
frequency at which DC braking is to be activated in
connection with a stop command.
Description of choice:
Set the desired frequency.
■■
■■
■ DC braking
In DC braking, the motor receives a DC current that
brings the shaft to a halt. Parameter 114 DC braking
current, decides the DC braking current as a
percentage of the rated motor current I
M,N
.
In parameter 115 DC braking time, the DC braking
time is selected, and in parameter 116 DC brake cut-
in frequency, the frequency is selected at which DC
braking becomes active.
If terminal 19 or 27 (parameter 303/304 Digital input)
has been programmed to DC braking inverse and
shifts from logic ‘1’ to logic ‘0’, the DC braking will be
activated.
When the start signal on terminal 18 changes from
logic ‘1’ to logic ‘0’, the DC braking will be activated
when the output frequency becomes lower than the
brake coupling frequency.
NB!
The DC brake is not to be used if the inertia of
the motor shaft is more than 20 times the inertia of
the motor itself.
114 DC braking current
(DC BRAKE CURRENT)
Value:
0 - ★ 50 %
The maximum value depends on the rated motor
current. If the DC braking current is active, the VLT
frequency converter has a switching frequency of 4 kHz.
Function:
This parameter is used for setting the DC braking
current that is activated upon a stop when the DC
brake frequency set in parameter 116 DC brake cut-in
frequency has been reached, or if DC brake inverse is
active via terminal 27 or via the serial communication
port. The DC braking current will be active for the
duration of the DC braking time set in parameter 115
DC braking time.
Description of choice:
To be set as a percentage value of the rated motor
current I
M,N
set in parameter 105 Motor current, I
VLT,N
.
100% DC braking current corresponds to I
M,N
.
I
VLT,MAX
I
M,N
x 100 [%]