★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
Programming
309 Terminal 53, min. scaling
(AI 53 SCALE LOW)
Value:
0.0 - 10.0 V ★ 0.0 V
Function:
This parameter is used for setting the signal value that
has to correspond to the minimum reference or the
minimum feedback, parameter 204 Minimum
reference, Ref
MIN
/413 Minimum feedback, FB
MIN
. See
Reference handling on page 89 or Feedback handling
on page 115.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.
If the time-out function is to be applied (parameters
317 Time out and 318 Function after time out), the
value must be set to > 1 V.
310 Terminal 53, max. scaling
(AI 53 SCALE HIGH)
Value:
0.0 - 10.0 V ★ 10.0 V
Function:
This parameter is used for setting the signal value that
has to correspond to the maximum reference value or
the maximum feedback, parameter 205 Maksimum
reference, Ref
MAX
/414 Maximum feedback, FB
MAX
. See
Reference handling on page 89 or Feedback handling
on page 115.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.
311 Terminal 54, analogue input voltage
(AI [V] 54 FUNCT.)
Value:
See description of parameter 308. ★No operation
Function:
This parameter chooses between the different
functions available for the input, terminal 54.
Scaling of the input signal is effected in parameter
312 Terminal 54, min. scaling and in parameter 313
Terminal 54, max. scaling.
Description of choice:
See description of parameter 308.
For reasons of accuracy, voltage losses in long signal
lines should be compensated for.
312 Terminal 54, min. scaling
(AI 54 SCALE LOW)
Value:
0.0 - 10.0 V ★ 0.0 V
Function:
This parameter is used for setting the signal value that
corresponds to the minimum reference value or the
minimum feedback, parameter 204 Minimum
reference, Ref
MIN
/413 Minimum feedback, FB
MIN
. See
Reference handling on page 89 or Feedback handling
on page 115.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.
If the time-out function is to be applied (parameters
317 Time out and 318 Function after time out), the
value must be set to > 1 V.
313 Terminal 54, max. scaling
(AI 54 SCALE HIGH)
Value:
0.0 - 10.0 V ★ 10.0 V
Function:
This parameter is used for setting the signal value that
corresponds to the maximum reference value or the
maximum feedback, parameter 205 Maximum
reference, Ref
MAX
/414 Maximum feedback, FB
MAX
. See
Reference handling on page 89 or Feedback handling
on page 115.
Description of choice:
Set the required voltage value.
For reasons of accuracy, voltage losses in long signal
lines can be compensated for.