VLT® 8000 AQUAOperating Instructions

Strany 2

VLT®8000 AQUA Use on isolated mainsSee section RFI Switch regarding use on isolated mains.It is important to follow the recommendations regardinginst

Strany 3 - Introduction

VLT®8000 AQUAFunction:Setting of the desired operating mode when themains voltage is reconnected.Description of choice:Auto restart [0] is selected if

Strany 4

VLT®8000 AQUAProgramming Load and motor 100-124This parameter group allows the configurationof regulation parameters and the choice oftorque characte

Strany 5

VLT®8000 AQUATor q u e. CT operation is achieved by maintaining aconstant U/f ratio over the operating range.NB!:It is important that the values set i

Strany 6 - VLT 8000 AQUA

VLT®8000 AQUAProgramming) Global factory setting different from NorthAmerican factory setting.Function:Select the rated motor frequency fM,N.Descripti

Strany 7

VLT®8000 AQUA- AMA can only be carried out if the rated motorcurrent of the motor is min. 35% of the ratedout-put current of the frequency converter.N

Strany 8

VLT®8000 AQUAProgrammingDescription of choice:Adjust the damping percentage until the motorresonance has disappeared.110 High break-away torque(HIGH S

Strany 9 - Warning:

VLT®8000 AQUA114 DC braking current(DC BRAK E CURRENT)Value:✭ 50 %The maximum value depends on the ratedmotor current. If the DC braking current isact

Strany 10 - 8000 AQUA

VLT®8000 AQUAProgrammingSelect Thermistor trip [2] if cutting out (trip) is desiredwhen the connected thermistor overheats.Select ETR Warning 1-4, if

Strany 11

VLT®8000 AQUAMotor size Change-over0.5kW-7.5kW >10Hz11 kW - 45 kW >5 Hz55 kW - 355 kW >3-4 Hz121 Slip compensation(SLIP COMPENSAT.)Value:-500

Strany 12

VLT®8000 AQUAProgramming124 Stator reactance(STATOR R EACT.)Value:✭depends on the choice of motorFunction:After setting motor data in parameters 102-1

Strany 13

VLT®8000 AQUAIntroduction Introduction to O perating InstructionsThese Operating Instructions are divided into foursections with information about VL

Strany 14

VLT®8000 AQUA References and Limits 200-228In this parameter group, the frequency and referencerange of the frequency converter are established.This

Strany 15

VLT®8000 AQUAProgramming Reference handlingReference handling is shown in the blockdiagram underneath.The block diagram shows how a change in a param

Strany 16

VLT®8000 AQUA203 Reference site(REFERENCE SITE)Value:✭Hand/Auto linked reference(LINKED TO HAND/AUTO)[0]Remote reference (REMOTE)[1]Local reference (L

Strany 17

VLT®8000 AQUAProgramming206 Ramp-up time(RAMP UP TIME)Value:1 - 3600 sec.✭ Depends on the unitFunction:The ramp-up time is the acceleration time from

Strany 18

VLT®8000 AQUA Reference typeThe example shows how the resulting reference iscalculated when Preset references are used togetherwith Sum and Relative

Strany 19

VLT®8000 AQUAProgrammingNB!:If Sum or Relative is selected, one of thepreset references will always be active. If thepreset references are to be witho

Strany 20

VLT®8000 AQUASee also parameter 216 Frequency bypass, bandwidth.221 Warning: Low current, ILOW(WARN. LOW CURR.)Value:0.0 - par. 222 Warning: High curr

Strany 21

VLT®8000 AQUAProgrammingThe warning functions in parameters 221-228 arenot active during ramp-up after a start command,ramp-down after a stop command

Strany 22

VLT®8000 AQUAto generate a warning signal via terminal 42 or45 and via the relay outputs.In Closed loop, the unit for the feedback is programmedin par

Strany 23

VLT®8000 AQUAProgrammingparam. 419 ) and continues operation in standard(normal) "closed loop" mode.NB!:The pipe fill closed loop operation

Strany 24

VLT®8000 AQUA Control principleA frequency converter rectifies AC voltage frommains into DC voltage, after which this DCvoltage is converted into a A

Strany 25

VLT®8000 AQUA Inputs and outputs 300-328In this parameter group, thefunctions that relate to theinput and output terminalsof the frequency convertera

Strany 26

VLT®8000 AQUAProgrammingDigital inputs Terminal no. 16 17 18 19 27 29 32 33parameter 300 301 302 303 304 305 306 307Value:No function (NO OPERATION) [

Strany 27

VLT®8000 AQUAbrake current and 115 DC braking time is different from0. Logic ‘0’ implements DC braking. See DC braking.Safety interlock has the same f

Strany 28

VLT®8000 AQUAProgrammingactive, the frequency converter will always be inOpen loop [0], regardless of the selection madein parameter 100 Configuration

Strany 29

VLT®8000 AQUA Analog inputsTwo analog inputs for voltage signals (terminals 53 and54) are provided for reference and feedback signals.Furthermore, an

Strany 30

VLT®8000 AQUAProgramming309 Terminal 53, min. scaling(AI 53 SCALE LOW)Value:0.0 - 10.0 V✭ 0.0 VFunction:This parameter is used for setting the signal

Strany 31

VLT®8000 AQUA315 Terminal 60, min. scaling and in parameter316 Terminal 60, max. scaling.315 Terminal 60, min. scaling(AI 60 SCALE LOW )Value:0.0 - 20

Strany 32

VLT®8000 AQUAProgramming Analog/digital outputsThe two analog/digital outputs (terminals 42 and45) can be programmed to show the present statusor a p

Strany 33

VLT®8000 AQUADescription of choice:No function Selected if the frequency converteris not to react to signals.Drive ready The frequency converter contr

Strany 34

VLT®8000 AQUAProgrammingExternal RefMIN- RefMAX0-20 mA andExternal RefMIN- RefMAX4-20 mA andExternal R efMIN-RefMAX0-32000 p whichgenerates an outp

Strany 35

VLT®8000 AQUAIntroduction• Energy savings in a constant air volume system• Compensation in the oversynchronousworking range• Reduces acoustic motor no

Strany 36

VLT®8000 AQUA322 Terminal 45, output, pulse scaling(AO 45 PULS SCALE)Value:1 - 32000 Hz✭ 5000 HzFunction:This parameter allows scaling of the pulse ou

Strany 37

VLT®8000 AQUAProgrammingIf the parameter 556 Bus time interval functionbecomes active, relay 1 and relay 2 will become cut offif they are activated vi

Strany 38

VLT®8000 AQUA323 Relay 1, output function(RELAY1 FUNCTION)Function:This output activates a relay switch. Relay switch01 can be used for indicating sta

Strany 39

VLT®8000 AQUAProgramming Application functions 400-434Includes this parameter group, the special functionsof the frequency converter PID regulation,

Strany 40

VLT®8000 AQUA Sleep modeSleep mode makes it possible to stop the motorwhen it is running at low speed, similar to a noload situation. If consumption

Strany 41

VLT®8000 AQUAProgramming403 Sleep mode timer(SLEEP MODE TIMER)Value:0 - 300 sec.(OFF)✭ OFFFunction:This parameter enables the frequency converter tost

Strany 42

VLT®8000 AQUANB!:Switching frequencies higher than 4.5 kHzimplement automatic derating of the maximumoutput of the frequency converter. SeeDerating of

Strany 43

VLT®8000 AQUAProgrammingFunction:Select the function which is to be activatedwhen the frequency converter is exposed toan overtemperature condition.De

Strany 44

VLT®8000 AQUA415 Units relating to closed loop(REF. / FDBK. UNIT)No unit [0] °C [21]✭% [1] GPM [22]rpm [2] gal/s [23]ppm [3] gal/min [24]pulse/s [4] g

Strany 45

VLT®8000 AQUAProgramming PID for process controlThe PID controller maintains a constant processcondition (pressure, temperature, flow, etc.) andadjus

Strany 46

VLT®8000 AQUA Example of application - Constant pressureregulation in water supply systemThe demand for water from waterworks varies considerably dur

Strany 47

VLT®8000 AQUAStart-up condi tionsIn some applications, optimum setting of the processregulator will mean that it takes an exces-sive timefor the requi

Strany 48

VLT®8000 AQUAProgramming PID overviewThe block diagram below shows reference andsetpoint in relation to the feedback signal.As can be seen, the remot

Strany 49

VLT®8000 AQUA1 setpoint a nd 1 feedb ackIf only 1 setpoint and 1 feedback signal are used,parameter 418 Setpoint 1 will be added to the remotereferenc

Strany 50

VLT®8000 AQUAProgramming417 Feedback function(2 FEED BACK, CALC.)Value:Minimum (MINIMUM)[0]✭Maximum (MAXIMUM)[1]Sum (SUM)[2]Difference (DIFFERENCE)[3]

Strany 51

VLT®8000 AQUAThe setpoint can be offset with digital, analog orbus signals, see reference handling.Used in Closed loop [1] parameter 100 Configuration

Strany 52

VLT®8000 AQUAProgrammingUsed in Closed loop [1] (parameter 100).Description of choice:Quick regulation is obtained by a high gain, but if thegain is t

Strany 53

VLT®8000 AQUA433 Motor Alternation Time(MOTOR ALT. TIME)Value:0 (OFF) - 999 hrs✭ OFFFunction:This is the time that sets the length of time betweenmoto

Strany 54

VLT®8000 AQUAProgramming Enhanced Sleep ModeUsing the frequency for initiating sleep-mode isacceptable in many cases, but if the suction pressureis v

Strany 55

VLT®8000 AQUA• Dry run protection. Shuts down at no or low flowand protects the motor and pump from overheating.• Improved energy savings with Enhance

Strany 56

VLT®8000 AQUAProgramming466 Maximum Pump Frequency(PUMP MAX. FREQ)Value:Value par. 201 fMIN- par. 202 fMAX(Hz)✭ 50Function:This parameter is linked to

Strany 57

VLT®8000 AQUAIntroduction PC software and serial communicationDanfoss offers various options for serial communication.Using serial communication, it

Strany 58

VLT®8000 AQUAnot be able to reset (automatically or manually) adry run trip before the timer has expired.472 Boost Time-Out(BOOST TIMEOUT)Value:0 (DIS

Strany 59

VLT®8000 AQUAProgramming Serial communication for FC protocol ProtocolsAs standard, all VLT 8000 AQUA units have a RS 485port which enables a choice

Strany 60

VLT®8000 AQUAPause time, min.: 2 charactersResponse time, min.: 2 charactersResponse time, max.: 20 msec.The time between individual characters in a t

Strany 61

VLT®8000 AQUAProgramming Data character (byte)The build-up of data blocks depends on the type oftelegram. There are three types of telegram and thete

Strany 62

VLT®8000 AQUAIf the command cannot be carried out, the slavewill send this reply (0111) Command cannot beexecuted and give the following error message

Strany 63

VLT®8000 AQUAProgrammingThe index character is used to indicate whetherthe command in question is a read or writecommand. For a read command, the inde

Strany 64

VLT®8000 AQUAConversion:The different attributes for each parameter can be seenin the section on factory settings. Since a parametervalue can only be

Strany 65

VLT®8000 AQUAProgramming Control word according to FC protocolThe control word is used for transmitting commandsfromamaster(e.g. aPC)toaslave.Bit Bit

Strany 66

VLT®8000 AQUAto disconnect the control word if it is not to be used inconnection with updating or reading of parameters.Bit 11, Relay 1:Bit 11 = "

Strany 67

VLT®8000 AQUAProgrammingBit 09, Local operation/serial communication control:Bit 09 = "0" means that OFF/STOP has been activatedon the contr

Strany 68

VLT®8000 AQUA LON - Local Operating NetworkLonWorks is an intelligent fieldbus system whichimproves the possibility of decentralising control,as comm

Strany 69

VLT®8000 AQUA Present output frequencyThe value of the present output frequency of thefrequency converter at any given time is transmittedas a 16-bit

Strany 70

VLT®8000 AQUAProgramming Serial communication 500-556In this parameter group, the serial communicationof the frequency converter is set up.In order t

Strany 71

VLT®8000 AQUA504 DC brake(DC BRAKE)Value:Digital input (DIGITAL INPUT)[0]Serial communication (SERIAL PORT)[1]Logic and (LOGIC AND)[2]✭Logic or (LOGIC

Strany 72

VLT®8000 AQUAProgrammingDigital input [0] Serial communication [1]Serial SerialKl.19 com.FunctionKl.19 com.Function0 0 Clockwise 0 0 Clockwise0 1 Cloc

Strany 73

VLT®8000 AQUALogic or [3]BusmsbBuslsbSetup/Pre-setmsbSetup/Pre-setlsbSetup no.Preset ref.no.0 0 0 0 100 0 1 200 1 0 300 1 1 40 1 0 0 201 0 1 201 1 0 4

Strany 74

VLT®8000 AQUAProgramming509 - 532 Data read-outValue:Parame-ter no.Description Display text Unit Updatinginterval509 Resulting reference (REFERENCE %)

Strany 75

VLT®8000 AQUAMotor voltage, parameter 517:Gives the voltage fed to the motor.DC link voltage, parameter 518:Gives the intermediate circuit voltage of

Strany 76

VLT®8000 AQUAProgramming533 Display text 1(DISPLAY TEXT ARRAY 1)Value:Max. 20 characters[XXXXXXXXXXXXXXXXXXXX]Function:Here, a text of max. 20 charact

Strany 77

VLT®8000 AQUADescription of choice:The output frequency of the frequency convertercan be frozen at the present value at any giventime, frozen at param

Strany 78

VLT®8000 AQUAProgramming Warning words 1+2 and Alarm wordWarning word, extended status word and alarm wordare shown in Hex format on the display. If

Strany 79

VLT®8000 AQUAIntroduction AccessoriesIP 20 bottom coverApplication optionType Description Order no.IP 4x top cover IP1)Option, VLT type 8006-8011 380

Strany 80

VLT®8000 AQUA Service functions 600-631This parameter group contains functions such asoperating data, data log and fault log.It also has information

Strany 81

VLT®8000 AQUAProgramming606 - 614 D ata logValue:Parameterno.DescriptionData log:Display text Unit Range606 Digital input (LOG: DIGITAL INP) Decimal 0

Strany 82

VLT®8000 AQUA615 Fault log: Error code(F. LOG: ERROR CODE)Value:[Index 1-10] Error Code: 0 - 99Function:This parameter makes it possible to see the re

Strany 83

VLT®8000 AQUAProgrammingFunction:In addition to its normal function, this parametercan be used for two different tests.Furthermore, it is possible to

Strany 84

VLT®8000 AQUA621 - 631 NameplateValue:Parameternr.DescriptionNameplate:Display text621 Unit type (DRIVE TYPE)622 Power component (POWER SECTION)623 VL

Strany 85

VLT®8000 AQUAProgrammingNB!:Parameters 700-711 for the relay cardare only activated if a relay option card isinstalled in the VLT 8000 AQUA.700 Relay

Strany 86

VLT®8000 AQUA Status messagesStatus messages appear in the 4th line of thedisplay - see example below.The left part of the status line indicates the

Strany 87

VLT®8000 AQUAAll about VLT 8000AQUAAutomatic Motor Adaptation completed(AMA STOP)Automatic motor adaptation has ben completed.The frequency converter

Strany 88

VLT®8000 AQUA List of warnings and alarmsThe table gives the different warnings and alarmsandindicates whether the fault locks the frequencyconverter

Strany 89

VLT®8000 AQUAAll about VLT 8000AQUA WarningsA warning will flash in line 2, while an explanationisgiveninline1.175ZA905.10DC LINK VOLTAGE LOWWARN. 6S

Strany 90

VLT®8000 AQUARittal Installation KitType Description Order No.Rittal TS8 enclosure for IP005)Installation kit for 1800mm high enclosure, VLT8152-8202,

Strany 91 - Installation

VLT®8000 AQUAgiving an alarm. The frequency converter cannotbe reset until the counter is below 90%.The fault is that the frequency converter is overl

Strany 92

VLT®8000 AQUAAll about VLT 8000AQUAALARM 22Auto-optimisation not OK (AMA FAULT)A fault has been found during automatic motoradaptation. The text shown

Strany 93

VLT®8000 AQUAA choice must thus be made by pressing [CHANGEDATA] and choosing "Continue" + [OK] or "Stop" + [OK].If parameters nee

Strany 94

VLT®8000 AQUAAll about VLT 8000AQUA Special conditions Aggressive environmentsIn common with all electronic equipment, a frequencyconverter contains

Strany 95

VLT®8000 AQUA Calculation of resulting referenceThe calculation made below gives the resultingreference when parameter 210 Reference type isprogramme

Strany 96

VLT®8000 AQUAAll about VLT 8000AQUA Earth leakage currentEarth leakage current is primarily caused by thecapacitance between motor phases and the mot

Strany 97

VLT®8000 AQUA Extreme running conditionsShort circuitVLT 8000 AQUA is protected against short circuitsby means of current measurement in each of thet

Strany 98

VLT®8000 AQUAAll about VLT 8000AQUA Peak voltage on motorWhen a transistor in the inverter is opened,the voltage across the motor increases by adU/dt

Strany 99

VLT®8000 AQUA Acoustic noiseThe acoustic interference from the frequencyconverter comes from two sources:1. DC intermediate circuit coils2. Integral

Strany 100

VLT®8000 AQUAAll about VLT 8000AQUA Derating for ambient temperatureThe ambient temperature (TAMB,MAX) is the maximumtemperature allowed. The average

Strany 101 - Programming

VLT®8000 AQUAIntroduction Cascade Controller OptionIn "Standard Mode", one motor is controlled bythe drive that has the Cascade Controller

Strany 102

VLT®8000 AQUA Derating for running at low speedWhen a centrifugal pump or a fan is controlled by a VLT8000 AQUA frequency converter, it is not necess

Strany 103

VLT®8000 AQUAAll about VLT 8000AQUA Air humidityVLT 8000 AQUA has been designed to meet theIEC 68-2-3 standard, EN 50178 pkt. 9.4.2.2/DIN40040, class

Strany 104

VLT®8000 AQUA Mains supply interference/harmonicsA frequency converter takes up a non-sinusoidalcurrent from mains, which increases the input current

Strany 105

VLT®8000 AQUAAll about VLT 8000AQUA CE labellingWhat is CE labelling?The purpose of CE labelling is to avoid technicalobstacles to trade within EFTA

Strany 106

VLT®8000 AQUA Danfoss frequency converter and CE labelingCE labelling is a positive feature when used for its originalpurpose, i.e. to facilitate tra

Strany 107

VLT®8000 AQUAEMC test results (Emission, Immunity)The following test results have been obtained using a system with a frequency converter (with option

Strany 108

VLT®8000 AQUA EMC ImmunityIn order to confirm immunity against interference from electrical phenomena, the following immunity test hasbeen made on a

Strany 109

VLT®8000 AQUAAll about VLT 8000AQUA Immunity, continuedBurst Surge ESD Radiated electro- Mains RF common Radiated radioBasic standard IEC 1000-4-4 IE

Strany 110

VLT®8000 AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Con-versionindexDatatype001 Languag e Engli

Strany 111

VLT®8000 AQUAAll about VLT 8000AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Con-ver-sionindexData

Strany 113

VLT®8000 AQUA Ordering numbers, LC filter modulesMains supply 3 x 200 - 240 VLC filter LC filter Rated current Max. output Powerfor VLT type enclosur

Strany 114

VLT®8000 AQUAConversion index Conversion factor74 0.12 10011001-1 0.1-2 0.01-3 0.001-4 0.0001Data typeData type shows the type and length of the teleg

Strany 115

VLT®8000 AQUAAll about VLT 8000AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Conver-sionindexDatat

Strany 116

VLT®8000 AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Conver-sionindexDatatype400 Reset function

Strany 117

VLT®8000 AQUAAll about VLT 8000AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringopera-tion4-setup Con-ver-sionindexDat

Strany 118

VLT®8000 AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Con-versionindexDatatype600 Operating data:

Strany 119

VLT®8000 AQUAAll about VLT 8000AQUA Option Card (for the four relay option card)PNU#ParameterdescriptionFactory setting Range Changesduringoperation4

Strany 120

VLT®8000 AQUA IndexAanalog inputs ... 31analog outputs:...

Strany 121

VLT®8000 AQUAIndexHigh voltage test... 61IIT mains...

Strany 122

VLT®8000 AQUATechnical data, mains supply 3 x 525 - 600 V... 43, 44Telegram build-up...

Strany 124

VLT®8000 AQUAIntroductionMainssupply3x690VVLTRated Current at 690VMax. outputfrequency (Hz)Powerdissipation (W)Ordering no. IP00Ordering no.IP208052 5

Strany 125

Rev. 2006-03-14www.danfoss.com/drives175R0894 MG83A202*MG83A202*

Strany 126

VLT®8000 AQUA LC filters VLT 8006-8011 380 - 480 V The drawing on the left gives the measurements of IP20 LC filters for the above-mentioned power ra

Strany 127

VLT®8000 AQUAIntroduction LC filters VLT 8006-8032, 200 - 240 V /8016-8062 380 - 480 VThe table and the drawing give the measurementsof IP 00 LC filt

Strany 128

VLT®8000 AQUA LC filter VLT 8042-8062 200-240 V /8072-8602 380 - 480 VThe table and the drawing give the measurements of IP20 LC filters. IP 20 LC fi

Strany 129

VLT®8000 AQUAIntroduction Harmonic filterHarmonic currents do not directly affect the electricityconsumption but has an impact on following condition

Strany 130

VLT®8000 AQUAPlease note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on400 V and assuming typical

Strany 131

VLT®8000 AQUAIntroduction Unpacking and ordering a VLT frequency converterIf you are in doubt as to which frequency converteryou have received and wh

Strany 132

VLT®8000 AQUA200-240 VTypeco dePosition in stringT29-10C0011-13C2011-13CN111-13C5411-13ST14-15SL14-15R016-17R116-17R316-174.0 kW/5.0 HP 8006 XXXXXX5.5

Strany 133

VLT®8000 AQUAIntroduction525-600 VTypecodePosition in stringT69-10C0011-13C2011-13CN111-13ST14-15R016-171.1 kW/1.5 HP 8002 XXX X1.5 kW/2.0 HP 8003 XXX

Strany 134

VLT®8000 AQUA ContentsIntroduction... 4Software

Strany 135

VLT®8000 AQUAOptional selections, 200-600 VDisplay Position: 18-19D01)Without LCPDL With LCPFieldbus option Position: 20-22F00 No optionsF10 Profibus

Strany 136

VLT®8000 AQUAIntroduction TYPE CODE Table/Ordering formMG.83.A2.02 - VLT is a registered Danfoss trademark29

Strany 137

VLT®8000 AQUA General technical dataMains supply (L1, L2, L3):Supply voltage 200-240 V units ...

Strany 138

VLT®8000 AQUAInstallationControl card, digital inputs:Number of programmable digital inputs ...

Strany 139

VLT®8000 AQUAFrequency ranges (digital output used as pulse output) ... 0-32

Strany 140

VLT®8000 AQUAInstallationCable lengths and cross-sections:Max. motor cable length, screened cable ...

Strany 141

VLT®8000 AQUAExternals:Enclosure ... IP00/Chassis, IP20/IP21/NEMA 1, IP

Strany 142

VLT®8000 AQUAInstallationVLT 8000 AQUA protection:• Electronic motor thermal protection against overload.• Temperature monitoring of heat-sink ensures

Strany 143

VLT®8000 AQUA Technical data, mains supply 3 x 200 - 240 VAccording to international requirements VLT type 8006 8008 8011Output current4)IVLT,N[A] 16

Strany 144

VLT®8000 AQUAInstallation Technical data, mains supply 3 x 200 - 240 VAccording to international requirements VLT type 8016 8022 8027 8032 8042 8052

Strany 145

VLT®8000 AQUAControl keys for parameter setup ... 84Indicator lamps ...

Strany 146

VLT®8000 AQUA Technical data, mains supply3x380-480VAccording to international requirements VLT type 8006 8008 8011Output current IVLT,N[A] (380-440

Strany 147

VLT®8000 AQUAInstallation Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8016 8022 8027 8032 8042Output

Strany 148

VLT®8000 AQUA Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8052 8062 8072 8102 8122Output current IVL

Strany 149

VLT®8000 AQUAInstallation Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8152 8202 8252 8302 8352Output

Strany 150

VLT®8000 AQUA Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8452 8502 8602 8652Output current IVLT,N[A

Strany 151

VLT®8000 AQUAInstallation Technical data, mains supply 3 x 525 - 600 VAccording to international requirements VLT type 8002 8003 8004 8005 8006 8008

Strany 152

VLT®8000 AQUA Technical data, mains supply 3 x 525 - 600 VAccording to international requirements 8016 8022 8027 8032 8042 8052 8062 8072Output curre

Strany 153

VLT®8000 AQUAInstallation Technical data, mains supply 3 x 525 - 690 VAccording to international requirements VVLT type 8052 8062 8072 8102 8122Outpu

Strany 154

VLT®8000 AQUA Technical data, mains supply 3 x 525 - 690 VAccording to international requirements VVLT type 8152 8202 8252 8302 8352 8402Output curre

Strany 155

VLT®8000 AQUAInstallation Technical data, mains supply 3 x 525 - 690 VAccording to international requirements VLT type 8502 8602 8652Output current I

Strany 156

VLT®8000 AQUADerating for ambient temperature ... 187Switching on the input ...

Strany 157

VLT®8000 AQUA FusesUL complianceTo comply with UL/cUL approvals, pre-fuses according to the table below must be used.200-240 VVLT Bussmann SIBA Litte

Strany 158

VLT®8000 AQUAInstallation525-600 VBussmann SIBA Littel fuse Ferraz-Shawmut8002 KTS-R3 5017906-004 KLS-R003 A6K-3R8003 KTS-R4 5017906-004 KLS-R004 A6K-

Strany 159

VLT®8000 AQUANonULcomplianceIf UL/cUL is not to be complied with, we recommend the above mentioned fuses or:VLT 8006-8032 200-240 V type gGVLT 8042-80

Strany 160

VLT®8000 AQUAInstallation Mechanical dimensionsAll the below listed measurements are in mm/inVLT type A B C a b aa/bb TypeIP 00/Chassis 200 - 240 V80

Strany 161

VLT®8000 AQUA Mechanical dimensionsMG.83.A2.02 - VLT is a registered Danfoss trademark52

Strany 162

VLT®8000 AQUAInstallation Mechanical dimensions (cont.)Type H, IP 20, IP 54Type I, IP 00Type J, IP 00, IP 21, IP 54MG.83.A2.02 - VLT is a registered

Strany 163

VLT®8000 AQUA Mechanical installationPlease pay attention to the requirementsthat apply to integration and field mountingkit, see the below list. The

Strany 164

VLT®8000 AQUAInstallation Installation of VLT 8452-8652 380-480 V andVLT 8502-8652, 525-6 90 VCompact IP 00/Chassis, IP 21/NEMA 1and IP 54/NEMA 12Coo

Strany 165

VLT®8000 AQUA General information about electrical installation High voltage warningThe voltage of the frequency converteris dangerous whenever the

Strany 166

VLT®8000 AQUAInstallation Extra protection with regard to indirect contactELCB relays, multiple protective earthing or earthing canbe used as extra p

Strany 167 - AUTO REMOTE RUNNING

VLT®8000 AQUA176FA145.16VLT 8000 AQUAOperating InstructionsSoftware version: 1.7xThese Operating Instructions can be used for all VLT 8000 AQUAfrequen

Strany 168

VLT®8000 AQUA RFI switchMains supply isolated from earth:If the frequency converter is supplied from an isolatedmains source ( IT mains) or TT/TN-S m

Strany 169

VLT®8000 AQUAInstallationCompact IP 20/NEMA 1VLT 8052 - 8122 380 - 480 VVLT 8027 - 8032 200 - 240 VVLT 8052 - 8072 525 - 600 VCompact IP 54/NEMA 12VLT

Strany 170

VLT®8000 AQUAAll enclosure typesVLT 8152-8652 380 - 480 VMG.83.A2.02 - VLT is a registered Danfoss trademark60

Strany 171 - 606 DATALOG:DIGITALINPUT

VLT®8000 AQUAInstallation High voltage testA high voltage test can be carried out by short-circuitingterminals U, V, W, L1,L2and L3and energizingby m

Strany 172

VLT®8000 AQUA EMC-correct electrical installation525-600 V units do not comply with EuropeanEMC and Low Voltage Directives.The following is a guideli

Strany 173

VLT®8000 AQUAInstallationMG.83.A2.02 - VLT is a registered Danfoss trademark63

Strany 174

VLT®8000 AQUA Earthing/Grounding of screened/armouredcontrol cablesGenerally speaking, control cables must be screened/armoured and the screen must b

Strany 175

VLT®8000 AQUAInstallation Electrical installation, enclosuresCompact IP 54/NEMA 12VLT 8006-8011, 380-4 80 VCompact IP 20/NEMA 1VLT 8006-8011, 380-4 8

Strany 176 - 175ZA701.10

VLT®8000 AQUACompact IP 54/NEMA 12VLT 8006-8032, 200-2 40 VVLT 8016-8072, 380-4 80 VCompact IP 20/NEMA 1VLT 8042-8062, 200-2 40 VCompact IP 00/Chassis

Strany 177 - All about VLT 8000

VLT®8000 AQUAInstallationCompact IP 20/NEMA 1VLT 8102-8122, 380-4 80 VCompact IP 54/NEMA 12VLT 8102-8122, 380-4 80 VIP 54/NEMA 12, IP 21/NEMA 1VLT 815

Strany 178

VLT®8000 AQUAIntroduction DefinitionsDefinitions are given in alphabetical order.AEO:Automatic Energy Optimization - function thatdynamically adjusts

Strany 179 - ALARM:12

VLT®8000 AQUAIP 54/NEMA 12, IP 21/NEMA 1 with disconnectand main fuseVLT 8252-8352, 380-4 80 VVLT 8252-8402, 525-6 90 VIP 00/Chassis with disconnect a

Strany 180

VLT®8000 AQUAInstallationCompact IP 20/NEMA 1, and IP 54/NEMA 12VLT 8006-8011, 380-4 80 VVLT 8002-8011, 525-6 00 VIP 54/NEMA 12VLT 8006-8032, 200-2 40

Strany 181

VLT®8000 AQUA Electrical installation, power cablesIP 00/Chassis and IP 20/NEMA 1VLT 8042-8062, 200-2 40 VIP 54/NEMA 12VLT 8042-8062, 200-2 40 VCompa

Strany 182

VLT®8000 AQUAInstallation Electrical installation, power cablesCompact IP 00 with disconnect and fuseVLT 8452-8652 380-480 V and VLT8502-8652, 525-69

Strany 183

VLT®8000 AQUACompact IP 21 / IP 54 without disconnect and fuseVLT 8452-8652 380-480 V and VLT8502-8652, 525-690 VNote: The RFI switch has no function

Strany 184

VLT®8000 AQUAInstallation Use of emc-correct cablesBraided screened/armoured cables are recommendedto optimise EMC immunity of the control cables and

Strany 185

VLT®8000 AQUA Tightening torque and screw sizesThe table shows the torque required when fittingterminals to the frequency converter. For VLT8006-8032

Strany 186

VLT®8000 AQUAInstallation Mains connectionMains must be connected to terminals 91, 92, 93.Nos. 91, 92, 93 Mains voltage 3 x 200-240 VL1, L2, L3 Mains

Strany 187

VLT®8000 AQUAProblems may arise at the start and at low rpm values ifthe motor sizes are widely different. This is because therelatively high ohmic re

Strany 188

VLT®8000 AQUAInstallation DC bus connectionThe DC bus terminal is used for DC back-up,with the intermediate circuit being suppliedfrom an external DC

Strany 189

VLT®8000 AQUAfrom the frequency converter, i.e. in a front panel,by means of the installation kit option.LSB:Least significant bit.Used in serial comm

Strany 190

VLT®8000 AQUA Electrical installation, control cablesTorque: 0.5 Nm (5 in-lbs)Screw size: M3.Generally speaking, control cables must be screened/armo

Strany 191

VLT®8000 AQUAInstallation Switches 1-4The dipswitch is located on the control card. It is usedfor serial communication and external DC supply.The swi

Strany 192

VLT®8000 AQUA Bus connectionThe serial bus connection in accordance with the RS485 (2-conductor) norm is connected to terminals68/69 of the frequency

Strany 193

VLT®8000 AQUAInstallation Connection example VLT 8000 AQUAThe diagram below gives an example of a typicalVLT 8000 AQUA installation.The mains supply

Strany 194

VLT®8000 AQUA Connection examples Single-pole start/stop- Start/stop using terminal 18.Parameter 302 = Start [1]- Quick-stop using terminal 27.Param

Strany 195

VLT®8000 AQUAInstallation 3-wire start/stop- Stop inverse by means of terminal 32.Parameter 306 = Stop inverse[14]- Latched start using terminal 18.P

Strany 196

VLT®8000 AQUA Control unit LCPThe front of the frequency converter featuresa control panel - LCP (Local Control Panel).This is a complete interface f

Strany 197

VLT®8000 AQUAInstallation[+/-] is used for selecting parametersand for changing a chosen parameter.These keys are also used to changethe local referen

Strany 198

VLT®8000 AQUA Display modeIn normal operation, any 4 different operating variablescan be indicated continuously: 1.1 and 1.2 and1.3 and 2. The presen

Strany 199

VLT®8000 AQUAInstallationoperating data names and units of operating dataare displayed. In the second line, operating data 2remains unchanged. When th

Strany 200

VLT®8000 AQUAIntroductionThe voltage of the frequency converteris dangerous whenever the equipmentis connected to mains. Incorrectinstallation of the

Strany 201

VLT®8000 AQUA Navigation between display modes175ZA697.10HAND LOCAL RUNNING0 ---- 60Display mode I40.0HzAUTO REMOTE RUNNINGFREQUENCY4

Strany 202

VLT®8000 AQUAInstallation Changing dataRegardless of whether a parameter has beenselected under the Quick menu or the Extendedmenu, the procedure for

Strany 203

VLT®8000 AQUA Quick MenuThe QUICK MENU key gives access to 12 of themost important setup parameters of the drive. Afterprogramming, the drive will, i

Strany 204

VLT®8000 AQUAInstallation Parameter DataEnter or change parameter dataor settings inaccordance with the following procedure.1. Press Quick Menu key.2

Strany 205

VLT®8000 AQUA ProgrammingUsing the [EXTEND MENU] key, itis possible to have access to allthe parameters for the frequencyconverter. Operation and Di

Strany 206

VLT®8000 AQUAProgrammingConnection examplesSetup chang e- Selection of Setup using terminals 32 and 33.Parameter 306 = Selection of Setup,lsb[4]Parame

Strany 207

VLT®8000 AQUA005 Max. value of user-defined readout(CUSTOM READOUT)Value:0.01 - 999,999.99✭ 100.00Function:This parameter allows a choice of the max.

Strany 208

VLT®8000 AQUAProgrammingFeedback [unit] (FEEDBACK [UNITS])[15]Motor voltage [V] (MOTOR VOLTAGE [V])[16]DC link voltage [V] (DC VOLTAGE [V])[17]Thermal

Strany 209

VLT®8000 AQUAthe relay is active, a "0" indicates inactive. Paramater007 uses an 8-bit word with the last two positionsnot used. Relays 6-9

Strany 210 - *MG83A202*

VLT®8000 AQUAProgrammingFunction:This parameter decides the local reference unit.Description of choice:Choose the required unit for local reference.01