VLT
®
6000 HVAC
45MG.60.B1.02 - VLT is a registered Danfoss trade mark
Installation
■■
■■
■ Mains supply 3 x 200 - 240 V
According to international requirements
VLVL
VLVL
VL
T typeT type
T typeT type
T type
60026002
60026002
6002
60036003
60036003
6003
60046004
60046004
6004
60056005
60056005
6005
60066006
60066006
6006
60086008
60086008
6008
60116011
60116011
6011
Output current
4 )
I
VLT,N
[A] 6.6 7.5 10.6 12.5 16.7 24.2 30.8
I
VLT, MAX
(60 s) [A] 7.3 8.3 11.7 13.8 18.4 26.6 33.9
Output (240 V) S
VLT,N
[kVA] 2.7 3.1 4.4 5.2 6.9 10.1 12.8
Typical shaft output P
VLT,N
[kW] 1.1 1.5 2.2 3.0 4.0 5.5 7.5
Typical shaft output P
VLT,N
[HP] 1.5 2 3 4 5 7.5 10
Max. cable cross-section
to motor and DC-bus [mm
2
/AWG] 4/10 4/10 4/10 4/10 4/10 16/6 16/6
Max. input current (200 V) I
L,N
[A] 6.0 7.0 10.0 12.0 16.0 23.0 30.0
Max. cable cross-section
power [mm
2
]/[AWG]
2 )
4/10 4/10 4/10 4/10 4/10 16/6 16/6
Max. pre-fuses [A]/UL
1 )
[A] 16/10 16/15 25/20 25/25 35/30 50 60
Mains contactor [Danfoss type] CI 6 CI 9 CI 12 CI 12 CI 6 CI 9 CI 16
[AC value] AC-3 AC-3 AC-3 AC-3 AC-1 AC-1 AC-1
Efficiency
3)
0.95
Weight IP 20 [kg] 7 7 9 9 23 23 23
Weight IP 54 [kg] 11.5 11.5 13.5 13.5 35 35 38
Power loss at max. load. [W] Total 76 95 126 172 194 426 545
Enclosure VLT type Bookstyle IP 20/Compact IP 20/IP 54
(Bookstyle IP 20 is available in power range VLT 6002-6005).
1. If UL/cUL is to be complied with, pre-fuses type Bussmann KTN-R 200 V, KTS-R 500 V or similar must be used.
In the remainder of the world, the first-mentioned pre-fuses must be used. These pre-fuses must be semi-conductor fuses of the gL
type. The fuses must be placed to protect a circuit capable of supplying max. 100,000 amps rms (symmetrical),
500 V maximum.
2. American Wire Gauge.
3. Measured using 30 m screened/armoured motor cable at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V
■■
■■
■ Mains supply 3 x 200 - 240 V
According to international requirements
VLVL
VLVL
VL
T typeT type
T typeT type
T type
60166016
60166016
6016
60226022
60226022
6022
60276027
60276027
6027
60326032
60326032
6032
60426042
60426042
6042
60526052
60526052
6052
60626062
60626062
6062
Output current
4 )
I
VLT,N
[A] 46.0 59.4 74.8 88.0 104 130 154
I
VLT, MAX
(60 s) [A] 50.6 65.3 82.3 96.8 115 143 170
Output (240 V) S
VLT,N
[kVA] 19.1 24.7 31.1 36.6 43,2 54,0 64,0
Typical shaft output P
VLT,N
[kW] 11 15 18.5 22 30 37 45
Typical shaft output P
VLT,N
[HP] 15 20 25 30 40 50 60
Max. cable cross-section
to motor and DC-bus [mm
2
/AWG] 16/6 35/2 35/2 50/0 70/1/0 95/3/0 120/4/
0
Min. cable cross-section
to motor and DC-bus [mm
2
/AWG] 10/8 10/8 10/8 16/6 10/8 10/8 10/8
Max. input current (200 V) I
L,N
[A] 46.0 59.2 74.8 88.0 101.3 126.6 149.9
Max. cable, cross-section,
power [mm
2
]/[AWG] 16/6 35/2 35/2 50/0 70/1/0 95/3/0 120/4/
0
Max. pre-fuses [A]/UL
1 )
[A] 60 80 125 125 150 200 250
Mains contactor [Danfoss type] CI 32 CI 32 CI 37 CI 45 - - -
[AC value] AC-1 AC-1 AC-1 AC-1
Efficiency
3)
0.95
Weight IP 00 [kg] - - - - 90 90 90
Weight IP 20 [kg] 23 30 30 48 101 101 101
Weight IP 54 [kg] 38 49 50 55 104 104 104
Power loss at max. load: [W] 545 783 1042 1243 1089 1361 1613
Enclosure IP 20+NEMA 1 kit, IP 54/NEMA 12
Komentáře k této Příručce