Danfoss VLT 5000 FLUX Provozní pokyny Strana 50

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 163
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 49
VLT
®
5000 FLUX
Control Panel
(LCP)
Initialisation to factory setting
The frequency converter can be initialised to
factory settings in two ways.
I
nitialisation by parameter 620
- Recommended initialisation
Select parameter 620
Press [CHANGE]
Select "Initialisation"
Press the [OK] key
Cut off the mains supply and wait until
the display turns off.
Reconnect the mains supply - the frequency
converter is now reset.
This parameter initialises all except:
500 Serial communication address
501 Baud rate for serial communication
601-605 Operating data
615-617 Fault logs
Manual initialisation
Disconnect from mains and wait until the
display turns off.
Press the following keys at
the same time:
[Display/status]
[Change data]
[OK]
Reconnecting the mains supply while
pressing the keys.
Release the keys
The frequency converter has now been
programmed for the factory setting.
This parameter initialises all except:
600-605 Operating data
NB!:
Settings for serial communication and
fault logs are reset.
MG.55.A7.02 - VLT is a registered Danfoss trademark
49
Zobrazit stránku 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 162 163

Komentáře k této Příručce

Žádné komentáře