Installation of VLT 5352-5502 380-500 V Compact
Nema 1 (IP 21) and IP 54
Cooling
All units in the above-mentioned series require a
minimum space of 225 mm above the enclosure and
must be installed on a flat level surface. This applies
to both Nema 1 (IP 21) and IP 54 units.
Gaining access to the VLT 5352-5502 requires
a minimum space of 579 mm in front of the
frequency converter.
Filter mats in IP 54 units have to be changed regularly
depending on the operating environment.
Side-by-side
Compact Nema 1 (IP 21) and IP 54
All Nema 1 (IP 21) and IP 54 units in the
above-mentioned series can be installed side by
side without any space between them, since these
units do not require cooling on the sides.