■ Parameter survey
PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
001 L
English No No 0 5
002 L
Remote control Yes Yes 0 5
003 L
000.000 Yes Yes -3 4
004 A
Setup 1 Yes No 0 5
005 P
Active setup Yes No 0 5
006 C
No copying No No 0 5
007 L
No copying No No 0 5
008 D
1 0.01 - 100.00 Yes Yes -2 6
009 D
Speed [rpm] Yes Yes 0 5
010 D
Reference [%] Yes Yes 0 5
011 D
Motor current [A] Yes Yes 0 5
012 D
Power [kW] Yes Yes 0 5
013 L
LCP control Yes Yes 0 5
014 L
Enable Yes Yes 0 5
015 L
Not possible Yes Yes 0 5
016 L
Not possible Yes Yes 0 5
017 L
Possible Yes Yes 0 5
018 L
Not locked Yes Yes 0 5
019 O
Operating state at power-up, local
control
Forced stop, use
saved ref.
Yes Yes 0 5
024 U
Not active Yes No 0 5
025 Q
000 0-999 Yes No 0 6
Changes during operation:
"Yes" means that the parameter can be changed,
while the frequency converter is in operation. "No"
means that the frequency converter must be stopped
before a change can be made.
4
-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the
same parameter can have four different data
values. "No" means that the data value will be
the same in all four setups.
C
onversion index:
This number refers to a conversion figure to
be used when writing or reading by means
of a frequency converter.
Conversion index Conversion factor
74 0.1
2 100
110
01
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
Data type:
Data type shows the type and length of the telegram.
Data type Description
3Integer16
4Integer32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9Textstring
MG.55.A7.02 - VLT is a registered Danfoss trademark
133