3.12.5 16-6* Inputs and Outputs
16-60 Digital input
Range: Function:
0 * [0 - 65535 ] View actual state of the digital inputs 18, 19, 27
and 29.
Bits definition
Bit 0 Unused
Bit 1 Unused
Bit 2 Digital input term. 29
Bit 3 Digital input term. 27
Bit 4 Digital input term. 19
Bit 5 Digital input term. 18
Bit 6~15 Unused
16-61 Terminal 53 Setting
Option: Function:
View the setting of input terminal 53. Current
= 0; Voltage = 1.
[0] * Current mode
[1] Voltage mode
16-62 Analog Input AI53
Range: Function:
1.000 * [0.000 - 20.000 ] View the actual value at input 53.
16-63 Terminal 54 Setting
Option: Function:
View the setting of input terminal 54. Current
= 0; Voltage = 1.
[0] * Current mode
[1] Voltage mode
16-64 Analog Input AI54
Range: Function:
1.000 * [0.000 - 20.000 ] View the actual value at input 54.
16-65 Analog Output AO42 [mA]
Range: Function:
0.000 mA* [0.000 -
20.000 mA]
View the actual value at output 42 in
mA. The value shown reflects the
selection in 6-90 Terminal 42 Mode and
6-91 Terminal 42 Analog Output.
16-66 Digital Output
Range: Function:
0 * [0 -
15 ]
View the binary value of all digital outputs.
Definition:
X: Not used
0: Low
1: High
16-66 Digital Output
Range: Function:
XX None used
X0 Terminal 42 not used, Terminal 45
low
X1 Terminal 42 not used, Terminal 45
High
0X Terminal 42 low, Terminal 45 not
used
0 Terminal 42 low, Terminal 45 low
1 Terminal 42 low, Terminal 45 high
1X Terminal 42 high, Terminal 45 not
used
10 Terminal 42 high, Terminal 45 low
11 Terminal 42 high, Terminal 45 high
16-71 Relay Output [bin]
Range: Function:
0 * [0 - 65535 ] View the setting of the relay.
Bits definition:
Bit 0~2 Unused
Bit 3 Relay 02
Bit 4 Relay 01
Bit 5~15 Unused
16-72 Counter A
Range: Function:
0.0 * [-32768 -
32767 ]
View the present value of Counter A. Counters
are useful as comparator operands, see
13-10 Comparator Operand.
The value can be reset or changed either via
digital inputs (parameter group 5-1*) or by
using an SLC action (13-52 SL Controller Action).
16-73 Counter B
Range: Function:
0.0 * [-32768 -
32767 ]
View the present value of Counter B. Counters
are useful as comparator operands
(LC-10 Comparator Operand).
The value can be reset or changed either via
digital inputs (parameter group 5-1*) or by
using an SLC action (13-52 SL Controller Action).
16-79 Analog Output AO45
Range: Function:
0.000 mA* [0.000 - 20.000 mA]
Parameters VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark 65