The FC101 Start-up Wizard for Open Loop Applications
No & Name Range Default Function
0-03 Regional Settings
[0] International
[1] US
0
1-20 Motor Power
0.12-110kW/0.16-150hp Size related Enter motor power from nameplate data
1-22 Motor Voltage
50.0 - 1000.0V Size related Enter motor voltage from nameplate data
1-23 Motor Frequency
20.0 - 400.0Hz Size related Enter motor frequency from nameplate data
1-24 Motor Current
0.01 - 10000.00A Size related Enter motor current from nameplate data
1-25 Motor Nominal Speed
100.0 - 9999.0 RPM Size related Enter motor nominal speed from nameplate data
4-12 Motor Speed Low Limit [Hz]
0.0 - 400 Hz 0 Hz Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]
0.0 - 400 Hz 65 Hz Enter the maximum limit for high speed
3-41 Ramp 1 Ramp up Time
0.05 - 3600.0 s Size related Ramp up time from 0 to rated motor frequency par. 1-23
3-42 Ramp 1 Ramp Down Time
0.05 - 3600.0 s Size related Ramp down time from rated motor frequency par. 1-23 to
0
1-73 Flying Start
[0] Disabled
[1] Enabled
0 Select Enable to enable the frequency converter to catch a
spinning motor i.e. fan applications
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1 Select if terminal 53 is used for current- or voltage input
6-10 Terminal 53 Low Voltage
0-10V 0.07V Enter the voltage that corresponds to the low reference
value
6-11 Terminal 53 High Voltage
0-10V 10V Enter the voltage that corresponds to the high reference
value
6-12 Terminal 53 Low Current
0-20mA 4 Enter the current that corresponds to the low reference
value
6-13 Terminal 53 High Current
0-20mA 20 Enter the current that corresponds to the high reference
value
3-02 Minimum Reference
-4999-4999 0 The minimum reference is the lowest value obtainable by
summing all references
3-03 Maximum Reference
-4999-4999 50 The maximum reference is the lowest obtainable by
summing all references
5-40 Function Relay [0] Function
relay
See 5-40 Function Relay
Alarm Select the function to control output relay 1
5-40 Function Relay [1] Function
relay
See 5-40 Function Relay
Drive running Select the function to control output relay 2
1-29 Automatic Motor Adaption
(AMA)
See 1-29 Automatic Motor
Adaption (AMA)
Off Performing an AMA optimizes motor performance
How to Programme VLT HVAC Basic Drive Programming Guide