Closed Loop Set-up Wizard
No & Name Range Default Function
0-03 Regional Settings
[0] International
[1] US
0
1-20 Motor Power
0.09-110kW Size related Enter motor power from nameplate data
1-22 Motor Voltage
50.0 - 1000.0V Size related Enter motor voltage from nameplate data
1-23 Motor Frequency
20.0 - 400.0Hz Size related Enter motor frequency from nameplate data
1-24 Motor Current
0.01 - 10000.00A Size related Enter motor current from nameplate data
1-25 Motor Nominal Speed
100.0 - 9999.0RPM Size related Enter motor nominal speed from nameplate data
4-12 Motor Speed Low Limit [Hz]
0.0 - 400Hz 0.0Hz Enter the minimum limit for low speed
4-14 Motor Speed High Limit [Hz]
0 - 400Hz 65Hz Enter the maximum limit for high speed
3-41 Ramp 1 Ramp up Time
0.05 - 3600.0 s Size related Ramp up time from 0 to rated motor frequency par. 1-23
3-42 Ramp 1 Ramp Down Time
0.05 - 3600.0 s Size related
Ramp down time from rated1-23 Motor Frequency to 0
1-73 Flying Start
[0] Disabled
[1] Enabled
0 Select Enable to enable the frequency converter to catch a
spinning motor
3-02 Minimum Reference
-4999-4999 0 The minimum reference is the lowest value obtainable by
summing all references
3-03 Maximum Reference
-4999-4999 50 The maximum reference is the highest value obtainable by
summing all references
3-10 Preset Reference
-100-100% 0 Enter the set point
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1 Select if terminal 53 is used for current- or voltage input
6-10 Terminal 53 Low Voltage
0-10V 0.07V Enter the voltage that corresponds to the low reference value
6-11 Terminal 53 High Voltage
0-10V 10V Enter the voltage that corresponds to the low high reference
value
6-12 Terminal 53 Low Current
0-20mA 4 Enter the current that corresponds to the high reference value
6-13 Terminal 53 High Current
0-20mA 20 Enter the current that corresponds to the high reference value
6-14 Terminal 53 Low Ref./Feedb.
Value
-4999-4999 0 Enter the feedback value that corresponds to the voltage or
current set in par. 6-10/6-12
6-15 Terminal 53 High Ref./Feedb.
Value
-4999-4999 50 Enter the feedback value that corresponds to the voltage or
current set in par. 6-11/6-13
6-16 Terminal 53 Filter Time
Constant
0-10 s 0.01 Enter the filter time comstant
20-81 PI Normal/ Inverse Control
[0] Normal
[1] Inverse
0
Select Normal [0] to set the process control to increase the output
speed when the process error is positive. Select Inverse [1] to
reduce the output speed.
20-83 PI Start Speed [Hz]
0-200Hz 0 Enter the motor speed to be attained as a start signal for
commencement of PI control
20-93 PI Proportional Gain
0-10 0.01 Enter the process controller proportional gain. Quick control is
obtained at high amplification. However if amplification os too
great, the process may become unstable
1-29 Automatic Motor Adaption
(AMA)
See 1-29 Automatic Motor
Adaption (AMA)
Off Performing an AMA optimizes motor performance
How to Programme VLT HVAC Basic Drive Programming Guide