3.12 Main Menu - Data Readouts - Group 16
3.12.1 16-0* General Status
16-00 Control Word
Range: Function:
0 * [0 - 65535 ] View the Control word sent from the frequency
converter via the serial communication port in
hex code.
Bit number
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit Bit = 0 Bit = 1
00 Preset reference choice lsb
01 Preset reference choice second bit of
preset references
02 DC brake Ramp
03 Coasting Enable
04 Quick-stop Ramp
05 Freeze output Ramp
06 Ramp stop Start
07 No function Reset
08 No function Jog
09 Ramp 1 Ramp 2
10 Data not valid Valid
11 Relay_A not active Relay_A activated
12 Relay_B not active Relay_B activated
13 Choice of Setup lsb
14 No function No function
15 No function Reversing
Table 3.2 Control Word
16-01 Reference [Unit]
Range: Function:
0.0 ReferenceFeed-
backUnit*
[-4999.0 - 4999.0
ReferenceFeed-
backUnit]
View the present
reference value applied
on impulse or analog
basis in the unit
resulting from the
configuration selected
in 1-00 Configuration
Mode (Hz).
16-02 Reference [%]
Range: Function:
0.0 %* [-200.0 - 200.0
%]
View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references.
16-03 Status Word
Range: Function:
0 * [0 - 65535 ] View the Status word sent from the frequency
converter via the serial communication port in
hex code.
Bit number
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit Bit = 0 Bit = 1
00 Control not ready Ready
01 VLT not ready Ready
02 Coasting Enable
03 No fault Trip
04 No warning Warning
05 Reserved
06 No trip lock Trip lock
07 No warning Warning
08
Speed ref.
Speed = ref.
09 Local control Bus control
10 Out of range Frequency OK
11 Not running Running
12 No function No function
13 Voltage OK Above limit
14 Current OK Above limit
15 Temperature OK Above limit
Table 3.3 Status Word
16-05 Main Actual Value [%]
Range: Function:
0.0 %* [-200.0 - 200.0 %] View the two-byte word sent with the
Status word to the bus Master
reporting the Main Actual Value.
16-09 Custom Readout
Range: Function:
0.0 CustomRea-
doutUnit*
[0.0 - 9999.0
CustomRea-
doutUnit]
View the user-defined
readouts as defined in
0-30 Custom Readout Unit,
0-31 Custom Readout Min
Value and 0-32 Custom
Readout Max Value. Custom
Readout
3.12.2 16-1* Motor Status
16-10 Power [kW]
Range: Function:
0.00 kW* [0.00 - 1000.00
kW]
Displays DC link power in kW. The
value shown is calculated on the basis
of the actual motor voltage and motor
current.
Parameters VLT HVAC Basic Drive Programming Guide