MAKING MODERN LIVING POSSIBLEDesign GuideVLT® HVAC Basic Drive FC 101www.danfoss.com/drives

Strany 2

TripA state entered in fault situations, e.g. if the frequencyconverter is subject to an over-temperature or when thefrequency converter is protecting

Strany 3 - 3 Selection

8 General Specifications and Troubleshooting8.1 Mains Supply Specifications8.1.1 Mains Supply 3x200-240 V ACFrequency converter PK25 PK37PK75 P1K5P2K

Strany 4 - 6 How to Programme

8.1.2 Mains Supply 3x380-480 V ACFrequency converter PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15KTypical shaft output [kW] 0.37 0.75 1.5 2.2 3.0

Strany 5

Frequency converter P18K P22K P30K P37K P45K P55K P75K P90KTypical shaft output [kW] 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0Typical shaft output [hp]

Strany 6

Frequency converter PK75 P1K5 P2K2 P3K0 P4KO P5K5 P7K5 P11K P15K P18KTypical shaft output [kW] 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11 15 18.5Typical shaft ou

Strany 7

Frequency converter P22K P30K P37K P45K P55K P75K P90KTypical shaft output [kW] 22.0 30.0 37.0 45.0 55.0 75.0 90.0Typical shaft output [hp] 30.0 40.0

Strany 8 - Definitions

8.1.3 Mains Supply 3x380-480 V ACFrequency converter PK75 P1K5 P2K2 P3K0 P4KO P5K5 P7K5 P11K P15KTypical shaft output [kW] 0.75 1.5 2.2 3.0 4.0 5.5 7.

Strany 9 - MG18C502 - Rev. 2013-09-06 7

Frequency converter P18K P22K P30K P37K P45K P55K P75K P90KTypical shaft output [kW] 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0Typical shaft output [hp]

Strany 10 - Power Factor

8.1.4 Mains Supply 3x525-600 V ACFrequency converter P2K2 P3K0 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90KTypical shaft output [k

Strany 11 - HIGH VOLTAGE

8.2 General SpecificationsProtection and features•Electronic thermal motor protection against overload.•Temperature monitoring of the heat sink ensur

Strany 12 - DISCHARGE TIME

Digital input 29 as thermistor input Fault: >2.9 kΩ and no fault: <800 ΩDigital input 29 as Pulse input Max frequency 32 kHz Push-Pull-Driven &a

Strany 13 - MG18C502 - Rev. 2013-09-06 11

2 Product Overview2.1 Safety 2.1.1 Safety NoteWARNINGDANGEROUS VOLTAGEThe voltage of the frequency converter is dangerouswhenever connected to mains.

Strany 14

Control card, 10 V DC outputA)Terminal number 50Output voltage 10.5 V ±0.5 VMax. load 25 mAA) All inputs, outputs, circuits, DC supplies and relay con

Strany 15 - Comparison of Energy Savings

8.3 Acoustic Noise or VibrationIf the motor or the equipment driven by the motor - e.g. a fan blade - is making noise or vibrations at certain freque

Strany 16 - Better Control

8.4 dU/Dt Cable length [m] AC line voltage [V] Rise time [usec]Vpeak [kV]dU/dt [kV/usec]200 V 0.25 kW5 240 0,121 0,498 3.25625 240 0,182 0,615 2,706

Strany 17 - Required

Cable length [m] AC line voltage [V] Rise time [usec]Vpeak [kV]dU/dt [kV/usec]400 V 11 kW5 400 0,116 0,69 487125 400 0,204 0,985 379950 400 0,316 1,

Strany 18 - Product Overview

Cable length [m] AC line voltage [V] Rise time [usec]Vpeak [kV]dU/dt [kV/usec]600 V 7.5 kW5 525 0,192 0,972 4,08350 525 0,356 1,32 2,9495 600 0,184

Strany 19 - 2.6.11 Application Examples

fsw[kHz]20 10010%20%30%40%50%60%70%80%90%100%110 %Iout[%]164045505oCoCoC130BC222.10Illustration 8.6 400 V IP20 H3 5.5-7.5 kWfsw[kHz]20 10010%20%30%40%

Strany 20 - The VLT Solution

Iout [%]fsw [kHz]20%2 4 6 8 10 1240%60%80%40oC45oC50oC100%110%130BC228.10Illustration 8.12 400 V IP20 H6 30-37 kWIout [%]fsw [kHz]20%2 4 6 8 10 1240%6

Strany 21 - 2.6.14 Constant Air Volume

Iout [%]fsw [kHz]20%2 4 6 8 10 1240%60%80%40oC45oC50oC100%110%130BC234.10Illustration 8.18 200 V IP20 H8 37-45 kWIout [%]fsw [kHz]20 %2 4 6 8 10 1240

Strany 22 - 2.6.16 Cooling Tower Fan

fsw[kHz]20 10010%20%30%40%50%60%70%80%90%100%110%Iout[%]164045505oCoCoC130BC255.10Illustration 8.24 400 V IP54 I2 0.75-4.0 kWfsw[kHz]20 10010%20%30%40

Strany 23 - 2.6.19 The VLT Solution

Iout [%]fsw [kHz]20%2 4 6 8 10 1240%60%80%40oC45oC50oC100%110%130BC242.10Illustration 8.30 400 V IP54 I7 45-55 kWIout [%]fsw [kHz]20%2 4 6 8 10 1240%6

Strany 24 - 2.6.20 Primary Pumps

WARNINGDISCHARGE TIMEFrequency converters contain DC-link capacitors that canremain charged even when the frequency converter isnot powered. To avoid

Strany 25 - Frequency

IndexAAbbreviations... 5Acoustic Noise...

Strany 26 - 130BB454.10

GGalvanic Isolation... 37GeneralAspects of Harmonics Emission...

Strany 27 - 2.7.3 PM/EC+ Motor Control

RRated motor speed... 6RCD...

Strany 28 - 2.7.6 Feedback Conversion

IndexVLT® HVAC Basic Drive FC 101 Design GuideMG18C502 - Rev. 2013-09-06 121

Strany 29 - 2.7.7 Reference Handling

www.danfoss.com/drives *MG18C502*130R0222 MG18C502 Rev. 2013-09-05

Strany 30

3. The frequency converter is sold as part of acomplete system. The system is being marketedas complete and could for example, be an air-conditioning

Strany 31

NOTICEMounting frequency converters in aggressiveenvironments increases the risk of stoppages and consid-erably reduces the life of the frequency conv

Strany 32

2.6.3 Example of Energy SavingsAs shown in Illustration 2.3, the flow is controlled bychanging the RPM. By reducing the speed only 20% fromthe rated s

Strany 33 - 2.7.10 Manual PI Adjustment

130BA779.110 60 0 60 0 60020406080100Discharge Damper SolutionIGV SolutionVLT SolutionEnergy consumedEnergy consumedEnergy consumedInput power %Volum

Strany 34 - 2.8 General Aspects of EMC

2.6.7 Star/Delta Starter or Soft Starter notRequiredWhen larger motors are started, it is necessary in manycountries to use equipment that limits the

Strany 35 - 2.8.1 Emission Requirements

2.6.9 Without a Frequency ConverterM- +MMx6 x6x6175HA205.12Valveposi-tionStarterFusesLVsupplyP.F.CFlow3-PortvalveBypassReturnControlSupplyairV.A.Voutl

Strany 36 - 2.8.2 EMC Test Results

2.6.11 Application ExamplesThe next pages provide typical examples of applicationswithin HVAC.For further information about a given application, ask t

Strany 38 - = 3 × 120 × 400 ×

2.6.12 Variable Air VolumeVAV, or Variable Air Volume systems, control both theventilation and temperature to satisfy the requirements ofa building. C

Strany 39 - 2.8.6 Immunity Requirements

2.6.14 Constant Air VolumeCAV, or Constant Air Volume systems, are centralventilation systems usually used to supply large commonzones with the minimu

Strany 40

2.6.16 Cooling Tower FanCooling Tower Fans cool condenser water in water cooledchiller systems. Water cooled chillers provide the mostefficient means

Strany 41 - <800 Ω >2.9 kΩ

2.6.18 Condenser PumpsCondenser water pumps are primarily used to circulatewater through the condenser section of water cooledchillers and their assoc

Strany 42

2.6.20 Primary PumpsPrimary pumps in a primary/secondary pumping systemcan be used to maintain a constant flow through devicesthat encounter operation

Strany 43 - R1.5 +_ 0.5

Frequency converterFrequency converterCHILLERCHILLERFlowmeterFlowmeterF F130BB456.10Illustration 2.15 Primary PumpsProduct OverviewVLT® HVAC Basic Dri

Strany 44 - 42 MG18C502 - Rev. 2013-09-06

2.6.22 Secondary PumpsSecondary pumps in a primary/secondary chilled waterpumping system distribute the chilled water to the loadsfrom the primary pro

Strany 45 - Decoupling Plate

2.7 Control Structures2.7.1 Control Principle1-00 Configuration Mode can be selected if open or closed loop is to be used.2.7.2 Control Structure Ope

Strany 46

2.7.4 Local (Hand On) and Remote (AutoOn) Control The frequency converter can be operated manually via thelocal control panel (LCP) or remotely via an

Strany 47 - Ordering Numbers

2.7.7 Reference Handling Details for Open Loop and Closed Loop operation.Speed open loopConfiguration modeInput command:freeze referenceProcesscontrolS

Strany 48 - How to Order

Contents1 Introduction51.1 Purpose of the Manual51.2 Document and Software Version51.3 Safety Symbols51.4 Abbreviations51.5 Additional Resources61.6 D

Strany 49 - 4.2.2 Harmonic Filters

2.7.8 Closed Loop Set-up Wizard6-29 Terminal 54 Mode[1] Voltage 6-25 T54 high Feedback0050 Hz20-94 PI integral time0020.00 sCurrentVoltageThis

Strany 50 - 4.2.3 External RFI Filter

Closed Loop Set-up WizardParameter Range Default Function0-03 Regional Settings [0] International[1] US0 0-06 GridType [0] -[[132] see start -up wiza

Strany 51

Parameter Range Default Function1-73 Flying Start [0] Disabled[1] Enabled0Select [1] Enable to enable the frequencyconverter to catch a spinning motor

Strany 52

2.7.9 Tuning the Drive Closed Loop ControllerOnce the frequency converter's closed loop controller has been set up, the performance of the contro

Strany 53 - 5.1.2 Shipping Dimensions

2.8 General Aspects of EMCElectrical interference is usually conducted at frequencies in the range 150 kHz to 30 MHz. Airborne interference from thef

Strany 54 - 5.1.4 Field Mounting

2.8.1 Emission RequirementsAccording to the EMC product standard for frequencyconverters, EN/IEC 61800-3:2004 the EMC requirementsdepend on the intend

Strany 55 - 5.2 Electrical Data

2.8.2 EMC Test ResultsThe following test results have been obtained using a system with a frequency converter, a screened control cable, a controlbox

Strany 56

2.8.3 General Aspects of HarmonicsEmissionA frequency converter takes up a non-sinusoidal currentfrom mains, which increases the input current IRMS. A

Strany 57

Individual Harmonic Current In/I1 (%)I5I7I11I13Actual 30-90 kW,IP20, 380-480 V(typical)36.7 13.8 6.9 4.2Limit for Rsce≥12040 25 15 10 Harmonic curren

Strany 58 - U 96 / V 97 / W 98

2.8.6 Immunity RequirementsThe immunity requirements for frequency convertersdepend on the environment where they are installed. Therequirements for t

Strany 59 - 130BA262.10

4 How to Order444.1 Configuration444.2 Ordering Numbers455 How to Install495.1 Mechanical Dimensions495.1.1 Frequency Converter Dimensions 495.1.2 Shi

Strany 60 - RELAY 1 RELAY 2

2.10 Earth Leakage Current WARNINGDISCHARGE TIMETouching the electrical parts could be fatal - even afterthe equipment has been disconnected from mai

Strany 61 - How to Install

the ETR cuts off and trips the frequency converter. Thecurves are showing the characteristic nominal speed attwice the nominal speed and at 0.2x the n

Strany 62 - 130BC203.10

Using an analog input and 10 V as power supply:Example: The frequency converter trips when the motortemperature is too high.Parameter set-up:Set 1-90

Strany 63 - 130BA248.10

3 Selection3.1 Options and Accessories3.1.1 Local Control Panel (LCP)Ordering no. Description132B0200 LCP for all IP20 unitsTable 3.1 Ordering Number

Strany 64

Step 4Connect cable to frequency converter.130BB778.10Illustration 3.4 Connect CableNOTICEUse the provided thread cutting screws to fastenconnector to

Strany 65

Frame IP class Power Height[mm] AWidth[mm] BDepth [mm]CIP21 kitorderingno.Type 1 kitordering no.3 x 200-240 V 3 x 380-480 V 3 x 525-600 VH1 IP20 0.25-

Strany 66

4 How to Order4.1 Configuration4.1.1 Drive Configurator It is possible to design a frequency converter according tothe application requirements by us

Strany 67 - MG18C502 - Rev. 2013-09-06 65

4.1.2 Type Code StringF C - P T H130BB899.10X S A B CX X X X1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 302221 23 272524 26 28 29 31 3736353433

Strany 68

4.2.1 Ordering Numbers: Options and Accessories Enclosureframe sizeMains voltageH1 [kW/Hp] H2 [kW/Hp] H3 [kW/Hp] H4 [kW/Hp] H5 [kW/Hp] H6 [kW/Hp] H7 [

Strany 69 - 130BC249.10

4.2.2 Harmonic Filters3x380-480 V 50 HzPower[kW]Drive inputcurrentContinuous[A]Defaultswitchingfrequency[kHz]THIDlevel[%]Ordernumberfilter IP00Codenum

Strany 70

7.4.5 Data Control Byte (BCC) 827.4.6 The Data Field 837.4.7 The PKE Field 847.4.8 Parameter Number (PNU) 847.4.9 Index (IND) 847.4.10 Parameter Value

Strany 71 - MG18C502 - Rev. 2013-09-06 69

4.2.3 External RFI FilterExternal filters to fulfil A1 50 m/B1 20 m.Power [kW]Size 380-480 VType A B C D E F G H I J K L1 Torque [Nm] Weight [kg] Orde

Strany 72 - How to Programme

5 How to Install5.1 Mechanical Dimensions5.1.1 Frequency Converter DimensionsAabBC D130BB614.10efade130BC205.10efae130BC246.10Enclosure Power [kW] H

Strany 73

The dimensions are only for the physical units, but wheninstalling in an application it is necessary to add space forfree air passage both above and b

Strany 74

5.1.2 Shipping DimensionsEnclosure frame sizeMains voltageH1 H2 H3 H4 H5 H6 H7 H8 H9 H10 I2 I3 I4 I5 I6 I7 I8T2 (200-240 V AC) [kW/Hp]0.25-1.5/0.33-22

Strany 75

5.1.3 Side-by-Side InstallationThe frequency converter can be mounted side-by-side and requires the clearance above and below for cooling. Power [kW

Strany 76 - MotorType = PM Motor

5.2 Electrical DataL1L2L33 PhasepowerinputPEPE+10 V DC0-10 V DC-0-10 V DC-50 (+10 V OUT)54 (A IN)53 (A IN)55 (COM A IN/OUT)0/4-20 mA0/4-20 mA42 0/4-2

Strany 77

5.2.1 Electrical Installation in GeneralAll cabling must comply with national and local regulations on cable cross-sections and ambient temperature. C

Strany 78

5.2.2 Connecting to Mains and MotorThe frequency converter is designed to operate allstandard 3-phased asynchronous motors. For maximumcross-section o

Strany 79

19599L1 91 / L2 92 / L3 93U 96 / V 97 / W 9803 02 0106 05 04234130BB762.10Illustration 5.3 H6 FrameIP20 380-480 V 30-45 kWIP20 200-240 V 15-18.5 kWIP2

Strany 80 - 78 MG18C502 - Rev. 2013-09-06

130BB764.1012349897969995939291L1L1L1UVwIllustration 5.5 H8 FrameIP20 380-480 V 90 kWIP20 200-240 V 37-45 kWIP20 525-600 V 75-90 kW1 Line2 Relays3 Ear

Strany 81 - MG18C502 - Rev. 2013-09-06 79

7.10.5 Preset Single Register (06 HEX) 937.10.6 Preset Multiple Registers (10 HEX) 947.11 Danfoss FC Control Profile947.11.1 Control Word According t

Strany 82 - 130BB795.10

130BA263.1095MAINS+DCBR-BR+UVW919293L1L2L3RELAY 1 RELAY 2Illustration 5.9 Mount mains plug and tighten wires+DCBR-BR+UVWMAINSL1 L2 L3

Strany 83

130BC299.1073251846Illustration 5.12 I2 FrameIP54 380-480 V 0.75-4.0 kW1RS-4852 Line in3 Earth4 Wire clamps5 Motor6 UDC7 Relays8 I/OTable 5.12 Legend

Strany 84

130BD011.10Illustration 5.14 I4 FrameIP54 380-480 V 0.75-4.0 kW1RS-4852 Line in3 Earth4 Wire clamps5 Motor6 UDC7 Relays8 I/OTable 5.14 Legend to Illus

Strany 85 - 130BA269.10

311130BA215.10RELAY 1RELAY 299603 02 0190 05 04Illustration 5.18 I6 FrameIP54 380-480 V 22-37 kW91L192L293L396U97V98W88DC-89DC+81R-8R+999513

Strany 86

5.2.3 Fuses and Circuit BreakersBranch circuit protectionTo protect the installation against electrical and fire hazard, all branch circuits in an ins

Strany 87 - 130BA092.10

Circuit Breaker FuseUL Non UL UL Non UL Bussmann Bussmann Bussmann Bussmann Max fusePower [kW] Type RK5 Type RK1 Type J Type T Type G3x380-480 V I

Strany 88 - 86 MG18C502 - Rev. 2013-09-06

Circuit Breaker FuseUL Non UL UL Non UL Bussmann Bussmann Bussmann Bussmann Max fusePower [kW] Type RK5 Type RK1 Type J Type T Type G3x380-480 V I

Strany 89

5.2.4 EMC Compliant Electrical InstallationGeneral points to be observed to ensure EMC-correct electrical installation.•Use only screened/armoured mot

Strany 90 - 88 MG18C502 - Rev. 2013-09-06

BackOKCom.OnWarn.AlarmHandOnOResetAutoOnMenuStatus QuickMenuMainMenuL1L2L3PEMin. 16 mm2Equalizing cableControl cablesAll cable entries inone side of

Strany 91

5.2.5 Control TerminalsIP20 200-240 V 0.25-11 kW and IP20 380-480 V 0.37-22 kW:130BB622.10Illustration 5.21 Location of Control Terminals1. Place a sc

Strany 92 - Modbus RTU

1 Introduction1.1 Purpose of the ManualThis design guide provides information on how to select,commission and order a frequency converter. It provide

Strany 93 - 96 and length 5 generates

6 How to Programme6.1 Programming with MCT 10 Set-upSoftwareThe frequency converter can be programmed from a PCvia RS-485 COM port by using the MCT 1

Strany 94 - Read Coil Status (01 HEX)

6.3 Menus6.3.1 Status MenuIn the Status menu the selection options are:•Motor Frequency [Hz], 16-13 Frequency•Motor Current [A], 16-14 Motor current•

Strany 95

Setup 1Power kW/50 HzSetup 1Set Motor Speed low LimitHzSetup 1Set Motor Speed high Limit HzSetup 1Set Ramp 1 ramp-up time sSetup 1Set Ramp 1 ramp-down

Strany 96

Start-up Wizard for Open Loop ApplicationsParameter Range Default Function0-03 Regional Settings [0] International[1] US0 0-06 GridType [0] 200-240 V

Strany 97

Parameter Range Default Function1-24 Motor Current 0.01-10000.00 A Size related Enter motor current from nameplate data1-25 Motor NominalSpeed100.0-99

Strany 98

Parameter Range Default Function6-11 Terminal 53 HighVoltage0-10 V 10 V Enter the voltage that corresponds to the highreference value6-12 Terminal 53

Strany 99 - MG18C502 - Rev. 2013-09-06 97

6-29 Terminal 54 Mode[1] Voltage 6-25 T54 high Feedback0050 Hz20-94 PI integral time0020.00 sCurrentVoltageThis dialog is forced to be set to [

Strany 100

Closed Loop Set-up WizardParameter Range Default Function0-03 Regional Settings [0] International[1] US0 0-06 GridType [0] -[[132] see start -up wiza

Strany 101

Parameter Range Default Function1-73 Flying Start [0] Disabled[1] Enabled0Select [1] Enable to enable the frequencyconverter to catch a spinning motor

Strany 102

Motor Set-upThe Quick Menu Motor Set-up guides through the needed motor parameters.Parameter Range Default Function0-03 Regional Settings [0] Internat

Strany 103

1.5 Additional Resources•VLT® HVAC Basic Drive FC 101 Quick Guide•VLT® HVAC Basic Drive FC 101 Programming Guideprovides information on how to progra

Strany 104

Changes MadeChanges Made lists all parameters changed since factorysetting. Only the changed parameters in current edit-setupare listed in changes mad

Strany 105

5. Reconnect the mains supply - the frequencyconverter is now reset.Except the following parameters:8-30 Protocol8-31 Address8-32 Baud Rate8-33 Parity

Strany 106

7 RS-485 Installation and Set-up7.1 RS-4857.1.1 OverviewRS-485 is a 2-wire bus interface compatible with multi-dropnetwork topology, that is, nodes c

Strany 107

7.1.4 Frequency Converter ParameterSettings for Modbus CommunicationDefine the RS-485 Communicaiton Set-upParameter Function8-30 Protocol Select the a

Strany 108 - 8.2 General Specifications

•Start•Stop of the frequency converter in various ways:•Coast stop•Quick stop•DC Brake stop•Normal (ramp) stop•Reset after a fault trip•Run at various

Strany 109

7.4.6 The Data Field The structure of data blocks depends on the type of telegram. There are 3 telegram types, and the type applies for bothcontrol te

Strany 110

7.4.7 The PKE FieldThe PKE field contains 2 subfields: Parameter commandand response (AK) and Parameter number (PNU):15 14 13 12 11 10 9 8 7 6 5 4 3 2

Strany 111

write the new value in the PWE block and send from themaster to the follower.When a follower responds to a parameter request (readcommand), the presen

Strany 112 - 8.4 dU/Dt

NOTICE4-14 Motor Speed High Limit [Hz] is a single word, and theparameter command for write in EEPROM is “E”.Parameter 4-14 is 19E in hexadecimal.The

Strany 113

7.6.4 Frequency Converter with ModbusRTUThe frequency converter communicates in Modbus RTUformat over the built-in RS-485 interface. Modbus RTUprovide

Strany 114

Bus referenceA signal transmitted to the serial communication port (FCport).Preset referenceA defined preset reference to be set from -100% to +100%of

Strany 115

7.8.3 Start/Stop FieldMessages start with a silent period of at least 3.5 characterintervals. This is implemented as a multiple of characterintervals

Strany 116

CoilNumberDescription SignalDirection1-16 Frequency converter control word(see Table 7.16)Master tofollower17-32 Frequency converter speed or set-poin

Strany 117

Bus adressBus register1PLC Register Content Access Description0 1 40001 Reserved Reserved for Legacy Drives VLT 5000 and VLT 28001 2 40002 Reserved

Strany 118

7.8.11 Modbus Exception CodesFor a full explanation of the structure of an exception coderesponse, refer to 7.8.5 Function Field.Code Name Meaning1 Il

Strany 119

Non standard data typesNon standard data types are text strings and are stored as4x registers (40001–4FFFF). The parameters are read usingfunction 03H

Strany 120

7.10.3 Force/Write Multiple Coils (0F HEX)DescriptionThis function forces each coil in a sequence of coils toeither ON or OFF. When broadcasting the f

Strany 121

ResponseThe normal response is an echo of the query, returnedafter the register contents have been passed.Field Name Example (HEX)Follower Address 01F

Strany 122

Programmedref. valueParameter Bit01Bit0013-10 Preset Reference [0]0 023-10 Preset Reference [1]0 133-10 Preset Reference [2]1 043-10 Preset Reference

Strany 123

7.11.2 Status Word According to FC Profile(STW) (8-30 Protocol = FC profile)Output freq.STWBitno.:Follower-master15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Strany 124 - *MG18C502*

Bit 15, Timer OK/limit exceededBit 15=’0’: The timers for motor thermal protection andthermal protection are not exceeded 100%.Bit 15=’1’: One of the