Datasheet
Part No. 560v08 03/08
TP7000 Series - Programmable Room Thermostats
Installer Settings -
Optimum Start Control
If DIL SW2 has been set to Optimum start control
enabled, the Optimum start control setting must
be made within the user programming mode. The
table below shows the calculated time before the
programmed time that the rst event of the day will
commence, dependant upon the difference in room
temperature and the programmed temperature for the
rst event. Setting options are 0:00, (OSC disabled,
0:30, 1:00, 1:30 or 2:00).
Desired Event 1
temperature.
Selecting 0
effectively
disables the
OSC function.
Available Start-up Periods
With a -2°C deviation and the 30 min. curve selected the
heating plant will switch on 15 min. before the Event 1 time.
Degrees below the desired
temperature at the beginning
of the Optimum Start Period
120 90 60 30 Event 1
min. min. min. min. time (0)
-1°C
-2°C
-3°C
-4°C
Thermostat Speci cation
Thermostat Features TP7000-RF TP7000 TP7000M
Order code - Built-in Sensor 087N741000 087N741400 087N740000 087N740400 087N740800 087N741900
- Remote Sensor
(A models)
087N741100 087N741500 087N740100 087N740500 087N740900 087N742000
Control type -
On/O or Chrono-proportional,
3/6 cycles per hour
••
Control type -
On/O or Chrono-proportional,
6/12 cycles per hour (C models)
••
RF - Wireless thermostat
Hard wired thermostat
Digital clock type 24 hour (can be set to AM/PM mode by user)
Selectable 7-day or 5/2-day operation Yes
Number of events per day Up to 6
Control temperature range O , 5-30°C (can be set to Fahrenheit by user)
Total switching di erential
(On/O mode)
<1.0°C
Factory pre-set programme Yes
Programmable holiday mode Yes, up to 99 days
Installer selectable
optimum start control
Yes - O , 30, 60, 90 or 120 minutes early switch on at set-point minus 4K
Thermostat mode and frost mode Yes, set to 8.0°C, but adjustable between 5-30°C
Power supply 2 x AA/MN1500/LR6 alkaline batteries 230V, 50 Hz
Memory back-up Capacitor during battery change for 1 minute
Rechargeable cell
(see note 1)
Switching action of output relay N/A SPDT
Switch rating of relay contact,
voltage and current
N/A 3 (1) A, 10-230 Vac
Transmitter frequency (RF models only) 433.92 MHz N/A
Transmitter range (RF models only) 30 metres max. N/A
Dimensions (mm) 138 wide x 88 high x 28 deep
Pollution situation Degree 2
Rated impulse voltage N/A 2.5Kv
Ball pressure test 75°C
Note 1: Unit must be powered up for 6 days to charge cell before full back up is available
Receiver Speci cation
(RF Models Only)
Receiver Features RX1 RX2 RX3
Order codes 087N747600 087N747700 087N747800
Single channel receiver module,
works in conjunction with one thermostat
Two channel receiver module,
works in conjunction with two thermostats
Three channel receiver module,
works in conjunction with three thermostats
Transmitter code self learning feature
Receiver frequencies 433.92 MHz
Supply voltage 220/240 Vac, 50 Hz
Output relay current rating 3 (1) A
Output relay con guration (commons linked internally) 1 x SPDT
1 x SPDT
1 x SPST
1 x SPDT
2 x SPST
Memory retention Memory retained electronically on power down
Dimensions (mm) 138 wide x 88 high x 32 deep
Zobrazit stránku 1