Safeguards:
Electronic thermal motor protection against
overload.
Temperature monitoring of the power module
ensures that the frequency converter cuts out
if the temperature reaches 100 °C. An over-
load temperature cannot be reset until the
temperature of the power module is below 70
°C.
The frequency converter is protected against
short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency
converter will cut out.
Monitoring of the intermediate circuit voltage
ensures that the frequency converter cuts out
if the intermediate circuit voltage is too low or
too high.
The frequency converter is protected against
earth fault on motor terminals U, V, W.
VLT
®
2800 Series
158 MG.27.E3.02 - VLT
®
is a registered Danfoss trademark