5.3.2. Status Word according to Drivecom 21 Profile
(Par. 8-10 = PROFIdrive profile)
Bit Bit value = 0 Bit value = 1
00 Not ready to switch ON Ready to switch ON
01 Switched OFF Switched ON
02 Operation disabled Operation enabled
03 No malfunction Malfunction
04 Voltage disabled Voltage enabled
05 Quick stop Run
06 Switch on disable Switch on enable
07 No warning Warning
08 Reserved
09 Remote disabled Remote enabled
10 Setpoint not reached Setpoint reached
11 Speed limit not active Speed limit active
12 Reserved
13 Reserved
14 Not running Running
15 Torque limit o.k. Torque limit exceeded
Explanation of the Bits:
Bit 00, Not ready to switch on/Ready to switch on:
Bit 00 = "0" state less than “Ready to switch on”.
Bit 00 = "1" state at least = “Ready to Switch on”.
Bit 01, Switch off/Switch on:
Bit 00 = "0" state less than “Switched on”.
Bit 00 = "1" state at least = “Switched on”.
Bit 02, Operation disable/Operation enable:
Bit 00 = "0" state less than “Operation enable”.
Bit 00 = "1" state at least = “Operation enable”.
Bit 03, No Malfunction/Malfunction:
Bit 03 = "0" means that the connection from Interbus option to is o.k.
Bit 03 = "1" means that the connection between Interbus option and has
been lost, or no is found.
Bit 04, Voltage disable/Voltage enable:
Bit 04 = "0" means that control word bit 01 = "1".
Bit 04 = "1" means that control word bit 01 = "0".
Bit 05, Quick stop/Run:
Bit 05 = "0" means that control word bit 02 = "1".
Bit 05 = "1" means that control word bit 02 = "0".
Bit 06, Start enable/Start disable:
Bit 06 = "0" state is “Switch on disable”.
Bit 06 = "1" state is “Switch on enable”.
Bit 07, No warning/Warning:
Bit 07 = "0" means that there is no warning situation.
Bit 07 = "1" means that a warning has occurred.
Bit 08, Danfoss reserved
Bit 09, Remote disable/Remote enable:
Bit 09 = "0" means that the has been stopped by means of the stop key
on the LCP, or that [Local] has been selected in par. 3-13 Reference site.
Bit 09 = "1" means that it is possible to control the converter via the serial
port.
Bit 10, Setpoint not reached/Setpoint reached:
Bit 10 = "0" means that the actual motor speed is different from the speed
reference set. This can be the case while the speed is ramped up/down
during start/stop.
Bit 10 = "1" means that the present motor speed equals the speed ref-
erence set.
Bit 11, Speed limit not active/speed limit active:
Bit 11 = "0" means that the output frequency is out of the range set in
par. 4-11/4-12 Motor Speed low Limit RPM/Hz or par. 4-13/4-14 Motor
Speed high Limit RPM/Hz.
Bit 11 = "1" means that the output frequency is within the mentioned
range.
Bit 12, Drivecom reserved
Bit 13, Drivecom reserved
Bit 14, Running/Not running:
Bit 14 = "0" means that the motor is not running.
Bit 14 = "1" means that the has a valid start signal or that the output
frequency is greater than 0 Hz.
Bit 15, Torque limit o.k./Torque limit exceeded:
Bit 15 = "0" means the torque limit received via PDC 4 is accepted and
within range.
Bit 15 = "1" means the torque limit received exceeds the limits in par.
4-15 and 4-16.
FC 300 Interbus Operating Instructions 5. How to Control the FC 300
MG.33.H3.02 - VLT is a registered Danfoss trademark
25