Specifi cations
H
D
W
H
W
D
18
Options
A wide range of HVAC options are available mounted and tested
from factory or as plug-and-play options for update.
• General purpose I/O
3 digital inputs, 2 digital outputs, 1 analog current output,
2 analog voltage inputs
• Relay outputs
3 relay outputs
• Analogue I/O
3 Pt1000 / Ni1000 inputs, 3 analog voltage outputs
• External 24 VDC supply
24 VDC external supply can be connected to supply
control- and option cards
• Brake chopper
Connected to an external brake resistor, the built in brake chopper
limits the load on the intermediate circuit in case the motor acts as
generator.
Filters
Danfoss Drives off ers a wide range of external power options for use
together with our drive in critical networks or applications:
• Advanced harmonic fi lters:
For critical demands on harmonic distortion
• dv/dt fi lters: For special demands on motor isolation protection
• Sine fi lters (LC fi lters): For noiseless motor
HVAC PC software
• MCT 10
– ideal for commissioning and servicing the drive
• VLT HVAC Planet
– an interactive design guide including application examples.
• VLT Energy Box
– comprehensive analysis tool to calculate the value of energy savings
in the application and the pay-back time of the drive.
• MCT 31
– harmonics calculations tool
Mains supply (L1, L2, L3)
Supply voltage 200 – 240 V ±10%
Supply voltage 380 – 500 V ±10%
Supply voltage 525 – 600 V ±10%
Supply frequency 50/60 Hz
Displacement Power Factor
(cos φ) near unity
(> 0.98)
Switching on input supply
L1, L2, L3
1-2 times/min.
Output data (U, V, W)
Output voltage 0 – 100% of supply voltage
Switching on output Unlimited
Ramp times 1 – 3600 sec
Closed loop 0 – 132 Hz
Digital inputs
Programmable digital inputs 6*
Logic PNP or NPN
Voltage level 0–24 V
*2 can be used as digital outputs
Analog input
Analog inputs 2
Modes Voltage or current
Voltage level 0 – 10 V (scaleable)
Current level 0/4 – 20 mA (scaleable)
Pulse inputs
Programmable pulse inputs 2
Voltage level 0-24 VDC (PNP positive logic)
Pulse input accuracy (0.1 – 110 kHz)
Max. error 0.1% of full scale
Analog output
Programmable analog outputs 1
Current range at analog output 0/4 – 20 mA
Relay outputs
Programmable relay outputs
(240 VAC, 2 A and 400 VAC, 2 A)
2
Fieldbus communication
Standard built in
FC Protocol, N2 Metasys,
FLN Apogee, Modbus RTU
Optional
LonWorks, BACnet, DeviceNet
Ethernet, Profi bus