VL 8000 AQUA
Quick Menu
The QUICK MENU key gives access to 12 of the
most important setup parameters of the drive. After
programming, the drive will, in many cases, be ready
for operation. The 12 Quick Menu parameters are
shown in the table below. A complete description
ofthefunctionisgivenintheparameter
sections of this manual.
Quick Menu Parameter Description
Item Number Name
1 001 Language Selects language used for all displays.
2 102 Motor Power Sets output characteristics of drive based on kW size
of motor.
3 103 Motor Voltage Sets output characteristics of drive based on voltage
ofmotor.
4 104 Motor Frequency Sets output characteristics of drive based on nominal
frequency of motor. This is typically equal to line
frequency.
5 105 Motor Current Sets output characteristics of drive based on nominal
current in amps of motor.
6 106 Motor Nominal Speed Sets output characteristics of drive based on nominal
full load speed of motor.
7 201 Minimum Frequency Sets minimum controlled frequency at which motor
will run.
8 202 Maximum Frequency Sets maximum controlled frequency at which motor
will run.
9 206 Ramp Up Time Sets time to accelerate motor from 0 Hz to nominal
motor frequency set in Quick Menu Item 4.
10 207 Ramp Down Time Sets time to decelerate motor from nominal motor
frequency set in Quick Menu Item 4 to 0 Hz.
11 323 Relay1 Function Sets function of high voltage Form C relay.
12 326 Relay 2 Function Sets function of low voltage Form A relay.
Parameter Data
Enter or change parameter dataor settings in
accordance with the following procedure.
1. Press Quick Menu key.
2. Use ‘+ and ‘- keys to find parameter
you choose to edit.
3. Press Change Data key.
4. Use ‘+ and ‘- keys to select correct parameter
setting. To move to a different digit within
parameter, use < and > arrows. Flashing cursor
indicates digit selected to change.
5. Press Cancel key to disregard change, or press
OK key to accept change and enter new setting.
Example of Changing Parameter Data
Assume parameter 206, Ramp Up Time, is set at 60
seconds. Change the ramp up time to 100 seconds
in accordance with the following procedure.
1. Press Quick Menu key.
2. Press ‘+
key until you reach Parameter
206, Ramp Up Time.
3. Press Change Data key.
4. Press < k
ey twice – hundreds digit will flash.
5. Press ‘+keyoncetochangehundredsdigitto‘1.
6. Press>keytochangetotensdigit.
7. Press ‘- k
ey until ‘6 counts down to ‘0 and
setting for Ramp Up Time reads ‘100 s.
8. Press OK key to enter new value into drive controller.
MG.80.A6.22 - VLT is a registered Danfoss trademark
86
Zobrazit stránku 39
1 2 ... 35 36 37 38 39 40 41

Komentáře k této Příručce

Žádné komentáře

Lemond manuali

La lista Lemond dei dispositivi contiene 23 manuali utenti e le guide per 5 modelli in 2 tipi di dispositivo

Accessori per il fitness
Modelli Tipo di Documento
RevMaster Pro Manuale Utente   LeMond RevMaster Pro User Manual, 9 pagine
RevMaster Pro Manuale Utente   LeMond RevMaster Pro User Manual, 29 pagine
RevMaster Pro Manuale Utente   LeMond RevMaster Pro User Manual, 30 pagine
RevMaster Pilot Manuale Utente   LeMond RevMaster Pilot Manuel d'utilisation, 29 pagine
RevMaster Pilot Manuale Utente   LeMond RevMaster Pilot Benutzerhandbuch, 29 pagine