The grey
side of the
ECL Card
Extended service
32k
Service parameter(s) 149-152
149 Time interval Δt
ALARM
before activation
of alarm function
Circuit Setting range Factory setting
I 1 ... 99 min. 10 min.
If an alarm condition from either line 147 or 148 is present for a
longer time than the time interval Δt
ALARM
, the alarm function is
activated.
1 ... 99: Time interval Δt
ALARM
.
If you choose OFF in line 147, the alarm function in lines 148 and
149 is not activated.
The alarm signal can only be sent via the module ECA 80.
Alarm
Temp.
Actual temp.
(S2)
Line 148
Desiredtemp.
(S2)
Line 147
Δt
ALARM
Line 149
Δt
ALARM
Line 149
Time
152 Max. temperature at S2 during DHW charging
Circuit Setting range Factory setting
I 10 ... 110 80
The desired DHW charging temperature at S2 is limited to the set
value.
Set the max. acceptable temperature at sensor S2.