Danfoss Heat Pump Průvodce řešením problémů

Procházejte online nebo si stáhněte Průvodce řešením problémů pro Tepelná čerpadla Danfoss Heat Pump. Danfoss Heat Pump Troubleshooting guide Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 34
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
Technical documentation | Air and ground source heat pumps
Looking for support?
Heat Pump Troubleshooting Guide
Error phase sequence 02
Working pressostat and high pressure pipe 03
Alarm high pressure 05
Alarm low pressure 08
Alarm motor protection 10
Alarm Circulation pump 12
Alarm Brinepump 13
Alarm Brine 14
Alarm Sensor 15
Alarm communication 16
Alarm Aux.heater 17
Sound 18
Temperature or the quantity of hot water 22
Thermal comfort 24
High operating time additional heater 28
Outdoor unit and defrosting problems 30
Room sensor digital 32
Electric hot water heaters 33
Zobrazit stránku 0
1 2 3 4 5 6 ... 33 34

Shrnutí obsahu

Strany 1 - Looking for support?

Technical documentation | Air and ground source heat pumpsLooking for support? Heat Pump Troubleshooting GuideError phase sequence 02Working presso

Strany 2

10VMIFB202Phase drop or blown fuseAction:Check that all phases are present on the terminal block for incoming supply.If not, check the fuses in the ca

Strany 3

11VMIFB202Troubleshooting Guide Alarm motor protectionDefective or incorrectly set motor protectionAction:Use a hook-on ammeter to establish when the

Strany 4 - Hot gas temperature too high

12VMIFB202The circulation pump’s integrated alarm has deployedAction:Check if there is air in the heat transfer uid circuit that can gather in the ci

Strany 5

13VMIFB202Troubleshooting Guide Alarm BrinepumpThe circulation pump’s integrated alarm has deployedAction:Check if there is air in the brine circuit

Strany 6 - Exchange valve jamming

14VMIFB202Alarm BrineAction:Check the set value on ALARM BRINE in the heat pump’s control computer under service-heat pump-temperatures-alarm brine.

Strany 7

15VMIFB202Alarm sensorAction:Measure the resistance of the sensor, check the ohm value against the temperature according to the table below.. If the a

Strany 8

16VMIFB202Alarm communicationAction:Check if the communication between the display card and relay card is broken.Test with another TP cable or communi

Strany 9

17VMIFB202Phase dropAction:Check that there is 230 V between incoming L2 on the circuit board and neutral on block 220. Check if the overheating prote

Strany 10 - Defective soft start

18VMIFB202Whistling expansion valveAction:Try tapping gently on the expansion valve.Open and close the valve fully in and out and adjust the expansion

Strany 11 - Defective compressor

19VMIFB202The compressor’s IPR valve opensAction:When the valve opens, this is indicated by the pressure on the low pressure side rising and reaching

Strany 12 - VMIFB202

2VMIFB202The incoming phases have the incorrect sequence (only applies to 3-phase heat pumps).Action:Reset the phasesWhen the compressor runs with the

Strany 13

20VMIFB202Touching pipes – vibrationsAction:Establish which pipe(s) causes vibrations and try to remove the tension that is causing the vibrations by,

Strany 14 - Alarm Brine

21VMIFB202Vibrating protective sleeves on the pressure switchesAction:Establish where the vibration noise occurs, if the vibration is in the protectiv

Strany 15 - Alarm sensor

22VMIFB202Defective 3-way valve motorAction:Check that the motor can be run to the limit positions in a manual test.If it is still, measure at the mol

Strany 16 - Alarm com Air, DHP-A

23VMIFB202Water heater too small in relation to requirementAction:Check the requirement and the water heater capacity.Replace with a larger heater or

Strany 17 - Phase drop

24VMIFB202The house heating comfort is not adjusted to the customer’s requirementsAction:Check the ROOM, CURVE and MIN settings. Adjust incorrect valu

Strany 18 - The compressor runs backwards

25VMIFB202Defective Honeywell 3-way valveAction:The motor should set the valve to the relevant end position depending on operating conditions. If it d

Strany 19 - Clicking

26VMIFB202Defective G2 shunt (HGW)Action:Check the function of the HGW shunt by test running it manually. If the motor does not shift mode during manu

Strany 20 - Touching pipes – vibrations

27VMIFB202Basic setting G2 shunt + motorAction:Important to reset the shunt after taking the shunt apart!The groove of the white six edged sleeve must

Strany 21 - The heat pump is not level

28VMIFB202Only runs on the additional heatAction:Ensure that the heat pump is not in additional heater only mode. If additional heater only mode is se

Strany 22

29VMIFB202Incorrect ow in the brine circuitAction:Check the dierence between the supply and return line using a digital thermometer. The dierence s

Strany 23

3VMIFB202Troubleshooting Guide Working pressostat and high pressure pipeThe operating pressure switch does not closeSwitch o the main switch for the

Strany 24

30VMIFB202Build-up of ice under and around the outdoor unit or water collectingAction:Drain the ground under and around the outdoor unit so that it ca

Strany 25

31VMIFB202Outdoor sensor/Defrost sensorAction:Check that the outdoor sensor/defrost sensor is installed according to the installation instructions and

Strany 26 - Defective G2 shunt (HGW)

32VMIFB202Room sensorThe image shows one of the models of room sensor availableThe room temperature sensor has a temperature sensor that provides a fu

Strany 27

33VMIFB202Water does not get hotAction:Check fuse(s).Check if there is cold water supply, if not, check why and rectify the fault.Check if the overhea

Strany 28

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its

Strany 29

4VMIFB202Hot gas temperature too high See in service under heat pump also check using own digital thermometer.Action:Check the refrigerant circuit see

Strany 30 - Defrosting problems

5VMIFB202Troubleshooting Guide Alarm high pressureBlocked strainer in the heating system return Action:

Strany 31 - Outdoor sensor/Defrost sensor

6VMIFB202Tip!Be careful not to spill water because there are electronics under the radiator pump; use something to protect the electronics.NOTE! This

Strany 32 - Installation

7VMIFB202Troubleshooting Guide Alarm high pressureThe operating pressure switch does not open but the heat pump opens at high pressure Action:Check t

Strany 33 - Water runs from the heater

8VMIFB202Blocked strainer on the brine circuit.Action:Check for brine in strainer (if necessary clean the strainer)Closed taps, main tap or ller cock

Strany 34

9VMIFB202Troubleshooting Guide Alarm low pressureExpansion valve defective or incorrectly setAction:Check that the cooling is correct for the specic

Komentáře k této Příručce

Žádné komentáře